CONNECTING THE ROCOIL MV
CURRENT TRANSFORMERS TO
THE LINE POWERED ELITEPRO
DENT INSTRUMENTS | 64 NW FRANKLIN AVENUE | BEND, OREGON 97701
P 541.388.4774 | 800.388.0770 | F 541.385.9333 | WWW.DENTINSTRUMENTS.COM
PERFORMANCE UPDA
TE
rev 072910
NOTE: DO NOT ATTACH THE VOLTAGE LEADS UNTIL THE ROCOIL MV
CURRENT TRANSFORMERS ARE CONNECTED TO THE ELITEPRO METER.
1. Open the levers on the
connector using a screw
driver.
Page 1
2. Place the
RED
+ve DC
power lead into one
connector and the
BLACK
-
ve lead into the other
connector.