Chapter 2 Installation and Wiring
|
VFD-L-I Series
2-6
Revision July 2009, SW V1.1
2.4.2 External Wiring
NFB or ELB
VFD-L-I
M
Power Supply
Magnetic Contactor
AC Reactor
Motor
Power Supply
Please follow the specific power
supply requirements shown in
Appendix A
No Fuse Breaker or Electricity Leakage Breaker
There may be an inrush current during power
up. Please refer to the following table for the
correct fuse selection.
Magnetic Contactor
Please do not use the magnetic contactor as
the power switch of the AC motor drive, as
it may reduce the operating life of the AC
motor drive.
AC Reactor
It is recommended to add an AC reactor
to improve the power factor when the output
capacity is more than 1000kVA. The wiring
distance should be less than 10m.
No-fuse Breaker Chart
Model 1-phase
230VAC
0.2KW/0.25HP 15A