After you finish adding DB, a screen displays as shown in the figure below.
4. Recompile the programs and download them to the PLC program.
5. Test if the programming is workable by using the Watch Table. Refer to the settings in the
figure below.
※
As shown in the example above, before reading the parameters, you must call WRREC
functional block to write FF 03 YY YY to change the mode of communication card, and then
call RDREC functional block to read the drive parameters (YY YY indicates the parameter
group and parameter number. For example, 01-00 means parameter group 01 and parameter
number 00.).
※
You can choose to read the parameters or not by setting REQ.