background image

 

22 

 

 

Default Gateway: Such as 192.168.0.1

 

DNS Server: Such as 8.8.8.8

It is recommended that this item be set by IT personnel or under the guidance of IT 

personnel. Setting errors will cause the network of UNOcentral to not work properly. The 

scope of influence includes but is not limited to: Remote use of web management interface, 

BACnet/IP, MQTT-Link, etc. 

 

Figure 9 

Network configuration window 

 

 

Содержание UNOcentral

Страница 1: ...Delta Electronics Inc UNOcentral Indoor Air Quality Monitor Web GUI Control System User Manual JERRY HSIAO DELTA ELECTRONICS INC...

Страница 2: ...n Globalview 2 Updated Chart description The ventilation equipment switch is modified to number of segments 2021 04 02 1 2 06 1 Instructions for use of wire for RS485 2 Modify the data chart range des...

Страница 3: ...ttings 23 2 1 1 3 MQTT Link settings only in MQTT mode 24 2 1 1 4 UNOnext WiFi settings only in MQTT mode 25 2 1 1 5 BACnet IP settings 27 2 1 1 6 Schedule settings 28 2 1 1 7 Event settings 33 2 1 1...

Страница 4: ...lendar 30 Figure 19 Edit plan date 30 Figure 20 Add a schedule for new plan 31 Figure 21 Project added 32 Figure 22 Event settings tab 33 Figure 23 Update tab 35 Figure 24 UNOnext Operation Panel Cont...

Страница 5: ...ption of the UNOcentral settings tab 17 Table 12 Description of the UNOnext settings tab 23 Table 13 Description of the UNOnext WiFi settings tab 27 Table 14 Description of Event settings parameters 3...

Страница 6: ...WiFi enabled UNOnext hereinafter referred to as UNOnext WiFi via the network through the support of the system integrator and distributor For the functional differences between multi models of UNOnext...

Страница 7: ...designated email inbox We hope that users can conveniently monitor and manage all important places through the combination of UNOnext UNOcentral and ventilation equipment in that way everyone can enjo...

Страница 8: ...gement or other network services it is recommended to connect the network cable to the LAN1 port on the back of UNOcentral The MAC address of LAN1 is provided on the UNOcentral s label As shown in Fig...

Страница 9: ...he UART configurations of the UNOcentral and UNOnext must be the same as followed Baud Rate 9600 Data bit 8 Parity None Stop bit 1 If the UART settings of UNOnext have been modified please modify to t...

Страница 10: ...0xDB 220 0xDC 221 0xDD 222 0xDE 223 0xDF 1 3 UNOnext WiFi connection method MQTT If the owner is unable to set up RS485 cables for UNOcentral and UNOnext due to certain reasons UNOcentral can also us...

Страница 11: ...rical data from different times for download according to the differences in the capabilities of UNOcentral and UNOnext WiFi products When UNOcentral is installed if the physical network cable install...

Страница 12: ...f you are using other hosts for management you need to confirm that the management host and UNOcentral can use port 8888 for HTTP communication This should be discussed with the IT unit of the operato...

Страница 13: ...other combinations not in the above list If there are other display problems it is recommended to upgrade to the newest versions of the operating system and browser and to browse in the recommended r...

Страница 14: ...s shown in Table 5 Table 5 UNOnext connection status icon Status Icon Connected Disconnected UNOnext abnormality warning B Temperature and humidity sensor values C Air quality sensor value UNOcentral...

Страница 15: ...ed using a different icon As shown in Table 7 Table 7 Description of power supply icons on ventilation equipment Status Icon On Off Ventilation equipment abnormality warning E Ventilator equipment fil...

Страница 16: ...ording to the method by which the ventilation equipment is connected to UNOnext RS485 If all devices are disconnected it will not be displayed And the reverse it will be displayed if any one device is...

Страница 17: ...gement Panel This chapter will explain the UNOcentral Management Panel There are slight differences in the management panel when using a RS485 connection versus a MQTT connection These differences wil...

Страница 18: ...mer name Customer name can be set Customer logo You can set the picture that the customer wants to use click upload after selecting the picture Customer Icon You can set the picture that the customer...

Страница 19: ...ng average Ozone O3 8 hour moving average Outdoor Information Determines the source of the outdoor information site displayed by Globalview and Signage There are Air Quality Index AQI PM2 5 concentrat...

Страница 20: ...ystem time zone of UNOcentral and the time zone of the current browser such as Chrome will be listed here as well as matching settings results Finally the user operator or professional will decide the...

Страница 21: ...m the system integrator or distributor 1 Reset UNOcentral Settings Including UNOcentral settings and UNOnext settings BACnet IP settings Schedule settings Event settings If UNOcentral is in MQTT mode...

Страница 22: ...LAN1 LAN2 and LAN3 on the UNOcentral device correspond to the Figure 8 marks enp2s0 enp3s0 enp4s0 It is recommend that the network cable be plugged into LAN1 Figure 8 Network status window Click Set i...

Страница 23: ...item be set by IT personnel or under the guidance of IT personnel Setting errors will cause the network of UNOcentral to not work properly The scope of influence includes but is not limited to Remote...

Страница 24: ...erning UNOnext data and enabling here is the data of up to 16 UNOnext units including Modbus ID Alias and Enabled As shown in Table 12 Table 12 Description of the UNOnext settings tab Data Description...

Страница 25: ...ame MQTT server UNOcentral can collect the data of those UNOnext sensors and linked ventilation equipment By default the UNOcentral uses the Local MQTT server as shown in Figure 11 Figure 11 MQTT Link...

Страница 26: ...access restrictions and firewall rules with the network manager or IT personnel to ensure that it can operate normally 2 1 1 4 UNOnext WiFi settings only in MQTT mode If UNOcentral has switched to MQ...

Страница 27: ...ial number an OK button will appear in the lower right corner After filling in click elsewhere on the screen or OK If the serial number differs after editing you will be asked to enter the device veri...

Страница 28: ...Description Serial number SN The serial number of UNOnext WiFi a required field after Enabled If filled in incorrectly UNOcentral will not receive data correctly Alias The alias of UNOnext WiFi can be...

Страница 29: ...e BACnet IP uses port 47808 and the UDP protocol to communicate on the internal network It is recommended to adjust the Server address and Port access restrictions and firewall rules with the network...

Страница 30: ...ed on the year this year and next year working day time period schedule mode and then create a new control plan when enabling control Maximum of 4 Current plans View details of the currently establish...

Страница 31: ...Figure 19 Edit plan date 2 Then in the displayed Add a schedule blocks select the time interval and the scheduling mode The mode can be set as turbo scheduling and it is displayed as C Turbo or be set...

Страница 32: ...rol plan has not yet taken effect Figure 20 Add a schedule for new plan 3 As shown in Figure 21 after successfully creating a new plan you will see the newly created plan in the Current plans block be...

Страница 33: ...an takes effect there is a set time period that UNOcentral will use UNOnext s sensor value to calculate the Turbo Smart mode to control the UNOnext ventilation equipment the unset time period will for...

Страница 34: ...Event Settings and Custom SMTP Server By default UNOcentral will try to send the notification letter by itself but if the user has a third party SMTP server that applied for or rented the user can al...

Страница 35: ...try to send the letter by itself SMTP Server SMTP server address SMTP Port The port number used by the SMTP server Security SMTP server address security settings Username SMTP server username Passwor...

Страница 36: ...e package for installation The system will automatically restart after installation Figure 23 Update tab If the user selects Specified Download URL and enters the customized download path and then fin...

Страница 37: ...igure 24 UNOnext Operation Panel Control Panel Tab 2 1 2 1 Control Panel As shown in Figure 24 the Control Panel is basically divided into an upper and lower block UNOnext Data Contains Modbus ID and...

Страница 38: ...and high speeds and off See the description in Table 17 for details Table 17 Descriptions of UNOnext Control Panel control items Options Description AutoMode Set UNOnext to AutoMode and there will be...

Страница 39: ...Onext a value other than 0 will be displayed For details see the UNOnext user manual Device Status If UNOnext is connected to the ventilation device via RS485 the connection status of up to 4 ventilat...

Страница 40: ...39 Figure 26 Use dry contact connection status tab...

Страница 41: ...Sensor Default value Unit Carbon dioxide CO2 1000 ppm PM2 5 35 g m3 PM10 75 g m3 Total volatile organic compounds TVOC 0 56 ppm Formaldehyde HCHO 0 08 ppm Carbon monoxide CO 9 ppm Ozone O3 0 06 ppm A...

Страница 42: ...control 2 1 2 4 Chart As mentioned previously UNOcentral will provide a data warehouse for UNOnext s sensor data with a frequency of 1 every 6 minutes The data can be browsed using the Chart tab in t...

Страница 43: ...sor data of the past N hours N is based on different system version Select Date Through selection in the calendar designate to display the sensor data of a certain day or 3 days from the past 5 years...

Страница 44: ...yed not displayed If the UNOnext does not have a specific sensor installed or there is no related sensor data for the selected time period it will not be displayed Historical data of the environmental...

Страница 45: ...heel zoom in out mouse drag clicking icon to switch data display Figure 33 Historical data of the air quality sensor Note If formaldehyde HCHO total volatile organic compounds TVOC and ozone O3 are di...

Страница 46: ...sis Main display functions are as follows Temperature and humidity sensor values Air quality sensor value UNOcentral will detect whether the sensor on the connected UNOnext is installed If it is not i...

Страница 47: ...layed if any one device is connected Dry contact Always displayed Outdoor Information note A Real time weather B Weather forecast C Outdoor Air Quality Index AQI outdoor PM2 5 concentration outdoor PM...

Страница 48: ...clically in the order of the following Table 19 Display mode case Case CO2 ERV switch Filter status ERV operation mode 1 783 Off Healthy Smart 2 850 Off Healthy Smart 3 1280 On Healthy Smart 4 1500 On...

Страница 49: ...ing the BACnet IP Device Instance of UNOcentral the default is 260001 you can use the BACnet IP client to read the information provided by UNOcentral through BACnet IP which includes the sensor values...

Страница 50: ...Other Please allow professionals to make the judgement U _BTN_STATUS AI U 17 1 N A UNOnext physical button status No control function 0 1 With control function 0 1 2 3 4 U _TEMP AI U 17 2 C Temperatur...

Страница 51: ...the ventilation equipment supplier U _ENABLED BI U 3 0 N A Is UNOnext enabled 0 Disabled 1 Enabled U _ONLINE BI U 3 1 N A For the connection status between UNOnext and UNOcentral either RS485 mode or...

Страница 52: ...s code is 50000 or continues to be 99999 contact technical support personnel for assistance in determining the status of the sensor 4 BACnet IP test method UNOcentral s BACnet IP data reading function...

Страница 53: ...he object including Presented Value will be displayed in block 3 C Right click on the BACnet object in block 2 and use the right click function menu to subscribe to the displayed value of the object I...

Отзывы: