4 Product overview
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
20
4.8 Information on the Type Plate
Information on the Type Plate
Description
10 seconds
Danger to life through electric shock
Potentially fatal voltage is present inside the inverter during operation and this voltage is
still present 10 seconds after disconnection of the power supply.
Only the fuse box may be opened. All other device parts may not be opened.
Before working on the solar inverter, you must read the supplied manual and follow the
instructions contained therein.
This inverter is not separated from the grid by a transformer.
The housing of the inverter must be grounded if this is required by local regulations.
WEEE marking
The inverter must not be disposed of as standard household waste, but in accordance with
the applicable electronic waste disposal regulations of your country or region.
DC input
200~1000 V DC
DC input voltage range
MPPT 520-800 V DC
MPP input voltage range at full power (with symmetrically configured DC inputs)
1000 V DC
Maximum DC input voltage
50 A*2 max.
Maximum DC input current (50 A at DC1 and DC2 respectively)
Isc: 60 A*2 max.
DC short-circuit current
AC output
220/380, 230/400 Vac
AC nominal voltage
3P3W or 3P4W
The inverter can be connected to 3-phase grids without neutral conductors (3P3W, 3
PE) and 3-phase grids with neutral conductors (3P4W, 3 N + PE).
50 / 60 Hz
AC nominal frequency
50 kW nom.
Nominal active power
55 kW/55 kVA
Maximum active power/reactive power
Max. 80 A
Maximum AC current
cos φ 0,8 ind. ~ 0.8 cap.
Setting range of the displacement factor cos φ
IP code: IP65 (Electronics)
Degree of protection for the electronics as per EN 60529
Protective Class: I
Safety class as per EN 61140
AC Overvoltage Category: III
AC overvoltage category as per IEC 62109-1
Assembled in China
Assembled in China