23
Quick installation guide for RPI H3 inverters EU EN 5013227802 02 2016-01-05
Mechanical Design
RPI H3
Dimensions (W x H x D)
420 x 367 x 157 mm
Weight
15 kg
Cooling
Natural convection
AC Connector type
Wieland RST25i3S B1G M01
DC Connector type
Multi-Contact MC4
Communication interfaces
2 x RS485, 1 x Dry contacts, 4 x Digital inputs
General Speciication
RPI H3
Delta model name
RPI H3_110
Delta part number
RPI302N63E0000
Maximum eficiency
97.0%
EU eficiency
96.2%
Operating temperature range
-25 ... +60 °C
Operating temperature range without derating
-25 ... +40 °C
Storage temperature range
-25 ... +60 °C
Relative humidity
0 ... 95 %, non-condensing
Maximum operating altitude
2000 m above sea level
Standards and Directives
RPI H3
Protection degree
IP65
Safety class
I
Pollution degree
II
Overload behavior
Current limitation; power limitation
Safety
IEC 62109-1 / -2, CE compliance
EMC
EN 61000-6-2, EN 61000-6-3
Immunity
IEC 61000-4-2 / -3 / -4 / -5 / -6 / -8
Harmonics
EN 61000-3-2
Variations and licker
EN 61000-3-3
Grid interfaces
See www.solar-inverter.com
Содержание RPI H3 110
Страница 1: ...Quick Installation Guide RPI H3_110 Europe...