Quick installation guide for RPI H3 inverters EU EN 5013227802 02 2016-01-05
Connecting multiple inverters to a datalogger
►
If you connect multiple inverters via RS485,
►
set a different Inverter ID for each inverter
(see “Setting the inverter ID”, p. 18).
If your datalogger has no integrated termination resistor, switch
on the termination resistor on the irst inverter in the RS485 line.
RS485
ON
OFF
ON
OFF
ON
OFF
Datalogger
Termination resistor = ON
Termination resistor = OFF
Termination resistor = OFF
Connecting a single inverter to a datalogger
RS485
ON
OFF
Datalogger
Termination resistor = ON
Connecting to a Delta SOLIVIA Gateway M1 G2
On the inverter you connect single wires, on the gateway you
have to use a RJ45 plug.
Connect inverter and gateway according to the following table:
Inverter
SOLIVIA Gateway M1 G2
1
8
DATA+
Terminal 3 or 5
Pin 7
DATA–
Terminal 4 or 6
Pin 6 or 8