Analog Voltage Transducer Wiring
Voltage Transducer, 4- or 5-Wire
Voltage Transducer, 3-Wire
To reduce electrical interference:
•
-In
and
Cmn
must be connected,
either internal to the transducer
or externally as close as possible
to the transducer.
•
Use individually shielded
twisted-pair wire.
•
Connect cable shield to earth
ground on one end only.
•
If transducer has only one
common, connect Pwr Supply
Common and RMC Cmn to it. For
best results, make this
connection at the transducer.