07 Descriptions of Parameter Settings | REG2000
7-1
07 Descriptions of Parameter Settings
00 Display Parameters
You can set this parameter during operation.
Power Regenerative Unit identity code
Power Regenerative Unit rated current display
Default:
read-only
Settings
Read-only (Display by model)
Pr.00-00 determines the capacity of the Power Regenerative Unit and is a default setting
parameter. Also, the rated current for that model is in the read-only parameter Pr.00-01. Pr.00-00
corresponds to the current displayed in Pr.00-01.
REG2000 Identity Code
Input voltage
230V
460V
Model code
0
2
4
6
8
10 12
1
3
5
7
9
11 13 15 17
Power
Regenerative Unit
corresponding
capacity
(kW)
7.5 11 15 18.5 22 30 37 7.5 11 15 18.5 22 30 37 45 55
Rated input current
(A)
20 32 38 49 60 80 100
10.5 17 20 25 32 43 49 60 75
Software version
Default:
#.##
Settings Read-only (Display according to shipped version)
Display Power Regenerative Unit input current (A
AC
)
Display mains frequency (Hz) (line frequency)
Default:
#.##
Settings
Read-only
Display DC BUS voltage (V
DC
)
Default:
#.#
Settings
Read-only
Display power (kW)
Default:
#.#
Settings
-300.0–300.0
Reserved
Reserved
Содержание REG2000 Series
Страница 44: ...04 Wiring REG2000 4 20 4 4 Display Panel Indicators Display Panel...
Страница 51: ...05 Optional Accessories REG2000 5 5 How to remove the plastic cap 1 Press the pin on top of the keypad...
Страница 67: ...05 Optional Accessories REG2000 5 21 5 5 External Power Supply Card 24 V EMC BPS01 Installing the EMC BPS01...
Страница 68: ...05 Optional Accessories REG2000 5 22 Removing the EMC BPS01...