Instruction Manual
PMU-13V155WC
□
A
1. Safety Instructions
• Must select correct AC input voltage range through selectable switch before turning on (Refer to
Fig. 1,
⑥
).
•
To ensure sufficient convection cooling, always maintain a safety distance of ≥ 20 mm from all
ventilated surfaces while the device is in operation.
•
The device is not recommended to be placed on low thermal conductive surface, for example,
plastics.
•
Note that the enclosure of the device can become very hot depending on the ambient temperature
and load of the power supply. Do not touch the device while it is in operation or immediately after
power is turned OFF. Risk of burning!
•
Do not touch the terminals while power is being supplied. Risk of electric shock.
•
Prevent any foreign metal, particles or conductors to enter the device through the openings during
installation. It can cause: Electric shock; Safety Hazard; Fire; Product failure
•
Battery need to be protected from short circuit while installation & servicing. Danger of explosion.
•
Signal cable should not interact with AC Input.
•
Warning: When connecting the device, secure Earth connection before connecting L and N. When
disconnecting the device, remove L and N connections before removing the Earth connection.
2. Device Descriptions
Refer to Fig. 1.:
䐟
Input & Output terminal block connector
䐠
DC voltage adjustment potentiometer (12Vdc - 14Vdc)
䐡
Green LED ON = DC OK (Normal operation through mains supply or through battery when
operating in buffering mode)
մ
Red LED ON = Battery reverse polarity
յ
Battery charging current adjustment potentiometer (Factory Setting: 1A)
Max charging current shall not exceed 1.5A (Refer to Fig. 1,
⑤
).
ն
AC selectable switch
䷻
Signal connector - JST: XHP-4 (for PMU-13V155WCCA only)
3. Installation of the Device
Refer to Fig. 2.:
䑵
Mounting holes for the power supply assembly onto the mounting surface. The power supply shall
be mounted on minimum 2 mounting holes using M3 screw minimum 5 mm length.
䑶
This surface belongs to customer’s end system or panel where the device is mounted.
䑷
Connector
•
Use flexible cable (stranded or solid), AWG No. 16-14.
•
The torque at the Connector shall not exceed 13 Kgf.cm. The insulation stripping length should not
exceed 0.275” or 7 mm (Refer to Fig. 3).
4. Battery Information*
Battery Capacity
3.2AH - 15AH
*For more information, please refer to the product datasheet.
5. Installation of Mounting Accessories
Refer to Fig. 4.:
•
Only use M3 screw ≤ 2.5 mm through the base mounting holes. This is to keep a safety distance
between the screw and internal components.
•
Recommended mounting tightening torque: 4~8 Kgf.cm.
www.DeltaPSU.com
REV.02
Fig. 1. Device Descriptions
Fig. 3. Wire Type
Fig. 4. Mounting Screw
Lug
Stripped wire
Mounting
accessories
Mounting
screw
Chassis of
the device
2.5mm
max.
7 mm
Side Mounting (Vertical)
Base Mounting (Vertical)
Side Mounting (Horizontal)
A
B
A
B
A
C
C
C
B
A
B
A
B
A
C
C
C
B
A
B
A
B
A
C
C
C
B
Fig. 2. Mounting Orientation
Base surface
Top surface
Ventilated surface
Side surface
1
2
3
5
4
6
PMU-13V155WCBA (no signal connector)
PMU-13V155WCCA (with signal connector)
Base surface
Top surface
Ventilated surface
Side surface
1
2
5
6
7
3
4
Pin No.
1
2
3
4
DC OK
Low Battery
GND
AC OK
Description
7
Signal connector
JST: XHP-4
400mm.(Ref.)