background image

PMT2 Panel Mount Power Supply 

PMT2 150W series / PMT-

V150W2C

□□

 

TECHNICAL DATASHEET

 

  

All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated.

 

  www.DeltaPSU.com (September. 2022, Rev. 02)  

3

 

Mechanical 

Case Chassis 

Aluminum 

Case Cover 

SGCC 

Dimensions (L x W x H) 

159 x 97 x 30 mm (6.26 x 3.82 x 1.18 inch) 

Unit Weight 

0.392 kg (0.864 lb) 

Indicator 

Green LED (DC OK) 

Cooling System 

Convection 

Terminal 

M 3.5 x 7 Pins (Rated 300 V / 20 A) 

Wire 

AWG 18-12  
Current rating can refer to page 6 “Wire AWG Table” 

Noise (1 Meter from power supply) 

Sound Pressure Level (SPL) < 25 dBA 

Environment 

Surrounding Air Temperature 

Operating  -30°C to +70°C ( -40°C Cold Start )

Storage  -40°C to +85°C

Power De-rating 

> 50°C de-rate power by 2% / °C
< 100 Vac de-rate power by 1.33% / V 

(86.67% load @ 90 Vac) 

Operating Humidity 

20 to 90% RH (Non-Condensing) 

Operating Altitude 

0 to 5,000 Meters (0 to 16,400 ft) 

Shock Test 

Non-Operating  IEC 60068-2-27, Half Sine Wave: 50 G for a duration of 11 ms, 3 shocks for 

each 3 directions 

Operating  IEC 60068-2-27, Half Sine Wave: 10 G for a duration of 11 ms, 3 shock for 

each 3 directions. 

Vibration 

Non-Operating  IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09 G); 

20 min per axis for all X, Y, Z direction 

Operating  IEC 60068-2-6, Sine Wave: 20 Hz to 500Hz (5 G); 

10 min per cycle, 60min for each axis (X, Y,Z) 

Over Voltage Category 

II (Compliance to EN 62477-1 OVC III with 2000 meters altitude) 

Pollution Degree 

Protections 

Overvoltage 

13.2 V – 17.4 V 

SELV Output, 

Latch Mode  

16.5 V - 21.0 V 

SELV Output, 

Latch Mode 

24.6 V - 33.6 V 

SELV Output, 

Latch Mode 

33.0 V - 40.5 V 

SELV Output, 

Latch Mode 

39.6 V - 48.6 V 

SELV Output, 

Latch Mode 

52.8 V - 64.8 V 

SELV Output, 

Latch Mode 

Overload / Overcurrent 

110-175% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery)

Over Temperature 

Latch Mode 

Short Circuit 

Hiccup Mode, Non-Latching 
(Auto-Recovery when the fault is removed) 

Protection Against Shock  Class I with PE*

4

 connection 

*4 : PE: Protection Earth

Reliability Data 

MTBF 

> 700,000 hrs as per Telcordia SR-332

I/P: 230Vac, O/P: 100% Load, Ta: 25°C)

Expected Cap Life Time 

10 years (230Vac, 50% load @ 40°C) 

Содержание PMT-12V150W2C Series

Страница 1: ...eneration PMT2 power supplies is designed in a low 30mm profile and accepts universal AC input The highly efficient convection cooling construction can operate from 30 C to 70 C The single output mode...

Страница 2: ...Vdc 1 36 Vdc 1 48 Vdc 1 Output Voltage Adjustment Range 10 8 13 2 Vdc 13 5 16 5 Vdc 21 6 26 4 Vdc 27 0 33 0 Vdc 32 4 39 6 Vdc 43 2 52 8 Vdc Output Current 0 12 5 A 0 10 0 A 0 6 5 A 0 5 0 A 0 4 3 A 0 3...

Страница 3: ...G for a duration of 11 ms 3 shocks for each 3 directions Operating IEC 60068 2 27 Half Sine Wave 10 G for a duration of 11 ms 3 shock for each 3 directions Vibration Non Operating IEC 60068 2 6 Rando...

Страница 4: ...55014 2 EN BS EN 61000 6 1 Electrostatic Discharge IEC 61000 4 2 Level 4 Criteria A1 Air Discharge 15kV Contact Discharge 8kV Radiated Field IEC 61000 4 3 Level 3 Criteria A1 80 MHz 1 GHz 10V M with...

Страница 5: ...EET All parameters are specified at 25 C ambient and nominal AC input unless otherwise indicated www DeltaPSU com September 2022 Rev 02 5 Block Diagram Device Descriptions 1 Input Output terminal bloc...

Страница 6: ...l AC input unless otherwise indicated www DeltaPSU com September 2022 Rev 02 6 Dimensions L x W x H 159 x 97 x 30 mm 6 26 x 3 82 x 1 18 inch Wire AWG Table Current rating for PVC Wire AWG 6AWG 52 5A 2...

Страница 7: ...mperature at 30 C 3 If the output capacity is not reduced when the surrounding air temperature 50 C the device will run into Over Temperature Protection When activated power supply will latch off unti...

Страница 8: ...is surface belongs to customer s end system or panel where the power supply is mounted Connector Base Mounting Horizontal If the device has to be mounted in any other orientation please contact info d...