Quick Installation Guide for Solar Power Inverter M125HV EU V1 EN 2019-04-01
Connecting a data logger via RS485
RS485 terminal block
2
1
3
4
5
6
1
VCC (+12 V; 0.5 A)
2
GND
3
DATA+ (RS485)
4
DATA– (RS485)
5
DATA+ (RS485)
6
DATA– (RS485)
Terminal pairs 3/4 or 5/6 can be used. The second terminal pair
is only required when connecting several inverters via RS485.
Data format
Baud rate
9600, 19200, 38400; standard: 19200
Data bits
8
Stop bit
1
Parity
Not applicable
Connecting a single inverter to a data logger
ON
1
Termination resistor = ON
Data logger
Connecting multiple inverters to a data logger
► If the data logger does not have an integrated RS485
termination resistor, switch the DIP switch for the RS485
termination resistor on the first inverter to
1 (ON)
(1)
.
► Set a different inverter ID at each inverter during com-
missioning, see “Commissioning via the commissioning
...
RS485
(1)
ON
1
ON
1
ON
1
Termination resistor = OFF
Termination resistor = OFF
Termination resistor = ON
Data logger
DIP switch for RS485 termination resistor and VCC
1
VCC (+12 V; 0.5 A)
2
RS485 termination resistor