INSTALLATION

If there is a surge so strong that something must be damaged, we prefer that our arrestor be
damaged rather than your equipment. Since we expect the arrestor might be damaged,
install it in a regular electrical enclosure to protect personnel from accidental contact with live
parts. Should the arrestor be damaged, it will not damage other components in the box. If the
arrestor cannot be placed in an enclosure, consider using our vent valve model. Its case will
not rupture. A small vent on the bottom of the case will open. 

To protect a submersible pump motor, connect the black wires to the line terminals and the
white wire to the casing and/or tubing.

To protect equipment on a radio tower or a drilling rig, mount the arrestor to a junction box at
the bottom of each string of lights going up to the tower. Connect the black leads to the
circuit conductors and the white wire to the rig steel. Arrange for the conductors feeding the
junction box to be parallel with the earth. Connect an arrestor to the generator leads
grounding the white wire to the generator frame. Connect an arrestor to each lighting panel
connecting black wires to the circuit conductors, and the white wire to the box and rig frame.

To protect a house, the arrestor should be mounted on an outside switch or junction box, or
in the breaker box. The black wires should be connected to the circuit. The white wire should
be connected to the neutral, the box, and/or a solid ground. Model numbers G have a
separate ground wire. 

To protect electronic equipment such as computers, transmitters, receivers, etc., connect the
black wires to the terminals of the device and the white wire to chassis. Mount the arrestor in
the cabinet. Consider using a surge capacitor connected to the breaker feeding them.

To protect a watt-hour meter, connect the black wires to the line terminals, and the white wire
to the meter box. 

To protect an electric motor on machinery, connect the black wires to the motor leads and
the white wire to the motor frame.

Where the switch and motor are within six feet of each other, one arrestor will protect both
provided a solid ground wire is fastened to the switch box, motor frame, and arrestor white
wire. However, optimum protection is afforded only when the arrestor is connected directly to
the device to be protected. 

To protect a motor control switch separately, connect the black wires to the line terminals

Home

General

Products

Ordering

Service/Inquiry Form

Downloadable Specs

Site Map

Содержание LA302R

Страница 1: ...me Connect an arrestor to each lighting panel connecting black wires to the circuit conductors and the white wire to the box and rig frame To protect a house the arrestor should be mounted on an outsi...

Страница 2: ...ground without damage When lightning or surge is in excess of 60 000 amps the arrestor is expected to experience damage In the event the arrestor should damage due to defects return it to the factory...

Страница 3: ...cient for the nominal circuit voltage and the current that is available at the line terminals of the secondary surge arrestor Connect black wires to lines load side of fuse breaker Connect white wire...

Страница 4: ...DELTALA Installation http www deltala com installa htm 4 of 7 10 24 2007 9 23 AM 5 Main box secure with locknut 6 Breaker box secure with ell bracket or strap...

Страница 5: ...eltala com installa htm 5 of 7 10 24 2007 9 23 AM 7 Breaker box secure with locknut 8 Motor control box secure with ell bracket or strap 9 Motor control box secure with locknut 10 Motor control box se...

Страница 6: ...DELTALA Installation http www deltala com installa htm 6 of 7 10 24 2007 9 23 AM 11 Motor control box secure with locknut 12 Motor junction box...

Страница 7: ...ttp www deltala com installa htm 7 of 7 10 24 2007 9 23 AM Order Your Products Now Information Request Form Home General Products Service Site Map Please give us your feedback on our website 2004 Delt...

Отзывы: