DVP04TC-S

 

Thermocouple Sensors   

Instruction Sheet 

 

 

WARNING 

 

Always read this manual thoroughly before using the DVP04TC-S. 

In order to avoid electric shock, do not touch the terminals or conduct any maintenance while power is 

applied to the PLC.    Never open the PLC.    Only qualified Delta personell should conduct any internal 

electrical work on the PLC.     

        This is an OPEN-TYPE device and must be placed in an environment away from high temperatures, high 

humidity, exceessive vibration, corrosive gases, liquids, airborne dust, and metallic particles when installed 

in an enclosure.   

       Do not apply AC power to any of the input/output terminals, this will cause permanent damage to the 

DVP04TC-S.  

Do NOT touch terminals when power on.

 

  Make sure that the DVP-04TC is properly grounded 

, to avoid any electromagnetic noise. 

 

INTRODUCTION 

2.1 Model Explanation and Peripherals 

  Thank you for choosing DELTA’s DVP Series PLC. The DVP04TC-S allows the connection of four 

thermocouple sensors 

(Type J.K.R.S.T).

 The DVP04TC-S series can read/write the data by using commands 

FROM / TO via DVP-PLC SS/SA/SX/SC MPU program. There are 49 CR (Control Register) in each module 

and 16 bits per register.   

  DVP04TC-S thermocouple sensor can update software version by RS-485. Power supply and main 

processing units are sold separately.   

  The DVP04TC-S works with both Centigrade and Fahrenheit. The input resolution for Centigrade is 0.1 

degrees and for Fahrenheit is 0.18 degrees. 

 

Nameplate Explanation 

P L C  m o d e l

Input power Supply Spec.

Analog Input /Output Module Spec.

Barcode, series and version

MODEL  

¡G

POWER  INPUT ¡G

THERMOCOUPLES¡G

04 TC -S0 T50 200 01

VX.X

24Vdc  2W 

MADE  IN  XXXXX X

RESOLUTION¡G

14 BITS

TYPE  J , K , R , S , T

 

 

Model Explanation

 

Serial Number

Model

S: for SS/SA /SX/SCseries MPU

XA: Analog input/output mixed module

Product Series

Input  + Output points 

Model type

AD: Analog input module
DA : Analog output module
PT: Platinum temperature sensors (PT-100) 

TC: Thermocouple sensors (Type )

Production series

Production week

Production year (2005)

Production place (Taoyuan)

Serial number of version

Production Model

RT: Resistor Thermocouple(NTC)

 

2.2 Product Profile and Outline 

90.00

4.00

3.00

25.20

1

2

3

4

60.00

5

6

7

8

9

3

10

L+

L-

SLD

C
H
1

C
H
2

C
H
3

C
H
4

11

12

13

3.4

90.00

60.00

3.00

14

L+

L-

L+

L-

L+

L-

SLD

SLD

SLD

 

Unit:mm 

1. Status indicator (Power, RUN and ERROR) 

8. Expansion port 

2. Model Number 

9. Expansion Clip 

3. DIN rail clip 

10. DIN rail location (35mm) 

4. I/O terminals 

11. RS-485 Communication port 

5. I/O point indicator 

12. Expansion Clip 

6.  Expansion  hole of the expansion  unit mounting 
pins 

13. DC Power input 

7. Specification Label 

14. Expansion port 

 

2.3 External wiring 

CH1

CH4

DC/ DC

5V

AG

+15V

-15V

AG

24+

24-

SLD

L-

L+

SLD

L-

L+

Converter

System

Class 3 Grounding

(100    of less)

terminal of

power module

Shielded*1

*2

*3

Shielded*1

Grounding

Thermocouple

+

-

100

MUX

Cold-junction
Compensation

Thermocouple

+

-

 

Note 1: Use only the wires that are supplied with your thermocouple sensor. Tighten PLC terminal screws to a 

torque of 1.95 kg-cm (1.7 in-lbs). 

Note 2: Terminal SLD is a grounding location for noise suppression.   

Note 3: Please connect 

  terminal of power supply module and 

  terminal of DVP04TC-S thermocouple 

sensors module to system earth ground. 

Warning: DO NOT connect wires to the No Connection (

) terminals. Use copper conductor only, 60/75

 

2.4 Terminals of analog module 

DVP04AD-S 

DVP02DA-S 

DVP04DA-S 

DVP04PT-S 

DVP04TC-S 

DVP06XA-S 

DVP08RT-S 

V+

I+

COM

FG
V+

I+

COM

FG

I+

COM

FG
V+

I+

COM

FG

V+

 

V+

I+

COM

FG
V+

I+

COM

FG

 

V+

I+

COM

FG
V+

I+

COM

FG

I+

COM

FG
V+

I+

COM

FG

V+

 

L+

L-

FG

FG

I-

L+

L-

I-

L+

L-

FG

FG

I-

L+

L-

I-

 

L+

L-

SLG

L+

L-

SLG

L+

L-

SLG

L+

L-

SLG

 

V+

I+

COM

V+

I+

COM

I+

COM

V+

I+

COM

V+

V+

I+

COM

V+

I+

COM

 

L+

L-

L-

L-

L+

L+

L-
L+

L+

L-

L-

L-

L+

L+

L-
L+

 

 

 

STANDARD SPECIFICATIONS 

3.1 Function Specifications 

Platinum Temperature Module (04TC) 

Centigrade (

°

C) 

Fahrenheit (

°

F) 

Power supply voltage 

24 VDC(20.4VDC~28.8VDC) ( –15%~+20%) 

Analog input channel 

4 channels per module 

Sensors type 

J-type K-type R-type S-type T-type thermocouple 

Temperature input range 

J type : -100

~700

   

K type : -100

~1000

 

R type : -10

~1700

   

S type : -10

~1700

 

T type : -100

~350

   

J type : -148

~1292

 

K type : -148

~1832

 

R type : -14

~3092

 

S type : -14

~3092

 

T type : -148

~662

 

Digital conversion range 

J type : K-1000~K7000 

K type : K-1000~K10000 

R type : K-100~K17000 

S type : K-100~K17000 

T type : K-1000~K3500 

J type : K-1480~K12920 

K type : K-1480~K18320 

R type : K-140~K30920 

S type : K-140~K30920 

T type : K-1480~K6620 

Resolution 

14 bits(0.1

°

C) 

14 bits(0.18

°

F) 

Overall accuracy 

±

0.5% of full scale of 25

°

C(77

°

F), 

±

1% of full scale during 0~55

°

(32~131

°

F) 

Response time 

350 ms

 

×

  channels 

Isolation Method 

Isolation between digital and analog circuitry. There is no isolation 

between channels. 

Digital data format 

2’s complement of 16-bit, (13 Significant Bits) 

Average function 

Yes (CR#2~CR#5 may be set and the range is K1~K4096) 

Self diagnostic function 

Yes 

Communication mode (RS-485) 

MODBUS ASCII/RTU Mode. Communication baud rate of 4800 / 9600 / 

19200 / 38400 / 57600 / 115200. For ASCII mode, date format is 7Bits, 

even, 1 stop bit (7 E 1). For RTU mode, date format is 8Bits, even, 1 stop 

bit (8 E 1). The RS-485 is disabled when the DVP04AD-S is connected in 

series to an MPU. 

Connection to a DVP-PLC MPU in 
series 

When DVP04-TC modules are connected to an MPU, the modules are 

numbered from 0 – 7. 0 is the closest to the MPU and 7 is the furthest. 

The Maximum number of modules is 8 modules and they do not occupy 

any digital I/O points of the MPU. 

3.2 Other Specification 

Power Specification 

Maximum Power Consumption 

2W at 24 VDC (20.4VDC~28.8VDC) ( -15 % ~ +20 %) 

 

Environment Condition 

Environment Condition 

Follow the DVP-PLC MPU. 

 

 

CR (CONTROLLED REGISTER) 

 

DVP-04TC platinum temperature sensors 

Explanation 

CR 

No. 

RS-485 

Parameter 

address

 

Latched 

Register name 

b15  b14  b13  b12  b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 

#0 

H 4096 

 

Model type 

System used,. DVP-04TC model code = H 8B 

#1 

H 4097 

  R/W  Thermocouple type 

Reserved 

CH4 

CH3 

CH2 

CH1 

Example: Setting of CH1 
1.  b2~b0: set (0,0,0) to use J-type 
2.  b2~b0: set (0,0,1) to use K-type 
3.  b2~b0: set (0,1,0) to use R-type 
4.  b2~b0: set (0,1,1) to use S-type 
5.  b2~b0: set (1,0,0) to use T-type 

#2 

H 4098 

  R/W  CH1 average number 

The number of readings used for “average” temperature on channels 
CH1~CH4.   
Setting range is K1~K4096 and factory setting is K10. 

#3 

H 4099 

  R/W  CH2 average number 

#4 

H 409A 

  R/W  CH3 average number 

#5 

H 409B 

  R/W  CH4 average number 

#6 

H 409C 

 

CH1 average degrees(

°

C) 

Average degrees for channels CH1~CH4.  (unit: 0.1 degrees C) 

#7 

H 409D 

 

CH2 average degrees(

°

C) 

#8 

H 409E 

 

CH3 average degrees(

°

C) 

#9 

H 409F 

 

CH4 average degrees(

°

C) 

#10  H 40A2 

 

CH1 average degrees(

°

F) 

Average degrees for channels CH1~CH4.  (unit: 0.1 degrees F) 

#11 

H 40A3 

 

CH2 average degrees(

°

F) 

#12  H 40A4 

 

CH3 average degrees(

°

F) 

#13  H 40A5 

 

CH4 average degrees(

°

F) 

#14  H 40A8 

 

Present temperature of 
CH1 (

°

C) 

Present temperature of channels CH1~CH4. (unit: 0.1 degrees C) 

#15  H 40A9 

 

Present temperature of 
CH2 (

°

C) 

#16  H 40AA 

 

Present temperature of 
CH3 (

°

C) 

#17  H 40AB 

 

Present temperature of 
CH4 (

°

C) 

#18 

Reserved 

#19  H 40AE 

 

Present temperature of 
CH1 (

°

F) 

Present temperature of channels CH1~CH4. (unit: 0.1degrees F) 

#20  H 40AF 

 

Present temperature of 
CH2 (

°

F) 

#21  H 40B0 

 

Present temperature of 
CH3 (

°

F) 

#22  H 40B1 

 

Present temperature of 
CH4 (

°

F) 

#23 

Reserved 

#24  H 40AE 

 

CH1 OFFSET Value 

Adjust offset value of channels CH1~CH4. The range is -1000~+1000 and 
factory setting is K0. (unit: 0.1 degrees C) 

#25  H 40AF 

 

CH2 OFFSET Value 

#26  H 40B0 

 

CH3 OFFSET Value 

#27  H 40B1 

 

CH4 OFFSET Value 

#28~#29 

Reserved 

#30  H 40B4 

 

Error status 

Data register stores the error status, refer to fault code chart for details. 

#31  H 40B5 

  R/W  Communication address 

setting 

RS-485 communication address.   
Setting range is 01~255 and factory setting is K1 

#32  H 40B6 

  R/W  Communication baud 

rate setting 

Communication baud rate (4800, 9600, 19200, 38400, 57600 and 115200 bps).   
b0: 4800 bps (bit/sec). 
b1: 9600 bps (bit/sec).    (factory setting) 
b2: 19200 bps (bit/sec). 
b3: 38400 bps (bit/sec). 
b4: 57600 bps (bit/sec). 
b5: 115200 bps (bit/sec). 
b6~b13: Reserved. 
b14: switch between low bit and high bit of CRC code (only for RTU mode) 
b15: RTU mode.     

#33  H 40B7 

  R/W  Reset to factory setting 

b15  b14  b13  b12  b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 

Definition of ERR 

LED 

CH4 

CH3 

CH2 

CH1 