DVP04TC-S
Thermocouple Sensors
Instruction Sheet
1
WARNING
Always read this manual thoroughly before using the DVP04TC-S.
In order to avoid electric shock, do not touch the terminals or conduct any maintenance while power is
applied to the PLC. Never open the PLC. Only qualified Delta personell should conduct any internal
electrical work on the PLC.
This is an OPEN-TYPE device and must be placed in an environment away from high temperatures, high
humidity, exceessive vibration, corrosive gases, liquids, airborne dust, and metallic particles when installed
in an enclosure.
Do not apply AC power to any of the input/output terminals, this will cause permanent damage to the
DVP04TC-S.
Do NOT touch terminals when power on.
Make sure that the DVP-04TC is properly grounded
, to avoid any electromagnetic noise.
2
INTRODUCTION
2.1 Model Explanation and Peripherals
Thank you for choosing DELTA’s DVP Series PLC. The DVP04TC-S allows the connection of four
thermocouple sensors
(Type J.K.R.S.T).
The DVP04TC-S series can read/write the data by using commands
FROM / TO via DVP-PLC SS/SA/SX/SC MPU program. There are 49 CR (Control Register) in each module
and 16 bits per register.
DVP04TC-S thermocouple sensor can update software version by RS-485. Power supply and main
processing units are sold separately.
The DVP04TC-S works with both Centigrade and Fahrenheit. The input resolution for Centigrade is 0.1
degrees and for Fahrenheit is 0.18 degrees.
Nameplate Explanation
P L C m o d e l
Input power Supply Spec.
Analog Input /Output Module Spec.
Barcode, series and version
MODEL
¡G
POWER INPUT ¡G
THERMOCOUPLES¡G
04 TC -S0 T50 200 01
VX.X
24Vdc 2W
MADE IN XXXXX X
RESOLUTION¡G
14 BITS
TYPE J , K , R , S , T
Model Explanation
Serial Number
Model
S: for SS/SA /SX/SCseries MPU
XA: Analog input/output mixed module
Product Series
Input + Output points
Model type
AD: Analog input module
DA : Analog output module
PT: Platinum temperature sensors (PT-100)
TC: Thermocouple sensors (Type )
Production series
Production week
Production year (2005)
Production place (Taoyuan)
Serial number of version
Production Model
RT: Resistor Thermocouple(NTC)
2.2 Product Profile and Outline
90.00
4.00
3.00
25.20
1
2
3
4
60.00
5
6
7
8
9
3
10
L+
L-
SLD
C
H
1
C
H
2
C
H
3
C
H
4
11
12
13
3.4
90.00
60.00
3.00
14
●
L+
L-
L+
L-
L+
L-
SLD
SLD
SLD
●
●
●
●
●
Unit:mm
1. Status indicator (Power, RUN and ERROR)
8. Expansion port
2. Model Number
9. Expansion Clip
3. DIN rail clip
10. DIN rail location (35mm)
4. I/O terminals
11. RS-485 Communication port
5. I/O point indicator
12. Expansion Clip
6. Expansion hole of the expansion unit mounting
pins
13. DC Power input
7. Specification Label
14. Expansion port
2.3 External wiring
CH1
CH4
DC/ DC
5V
AG
+15V
-15V
AG
24+
24-
SLD
L-
L+
SLD
L-
L+
Converter
System
Class 3 Grounding
(100 of less)
terminal of
power module
Shielded*1
*2
*3
Shielded*1
Grounding
Thermocouple
+
-
100
MUX
Cold-junction
Compensation
Thermocouple
+
-
Note 1: Use only the wires that are supplied with your thermocouple sensor. Tighten PLC terminal screws to a
torque of 1.95 kg-cm (1.7 in-lbs).
Note 2: Terminal SLD is a grounding location for noise suppression.
Note 3: Please connect
terminal of power supply module and
terminal of DVP04TC-S thermocouple
sensors module to system earth ground.
Warning: DO NOT connect wires to the No Connection (
) terminals. Use copper conductor only, 60/75
℃
2.4 Terminals of analog module
DVP04AD-S
DVP02DA-S
DVP04DA-S
DVP04PT-S
DVP04TC-S
DVP06XA-S
DVP08RT-S
V+
I+
COM
FG
V+
I+
COM
FG
I+
COM
FG
V+
I+
COM
FG
V+
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
I+
COM
FG
V+
I+
COM
FG
V+
L+
L-
FG
FG
I-
L+
L-
I-
L+
L-
FG
FG
I-
L+
L-
I-
L+
L-
SLG
L+
L-
SLG
L+
L-
SLG
L+
L-
SLG
V+
I+
COM
V+
I+
COM
I+
COM
V+
I+
COM
V+
V+
I+
COM
V+
I+
COM
L+
L-
L-
L-
L+
L+
L-
L+
L+
L-
L-
L-
L+
L+
L-
L+
3
STANDARD SPECIFICATIONS
3.1 Function Specifications
Platinum Temperature Module (04TC)
Centigrade (
°
C)
Fahrenheit (
°
F)
Power supply voltage
24 VDC(20.4VDC~28.8VDC) ( –15%~+20%)
Analog input channel
4 channels per module
Sensors type
J-type K-type R-type S-type T-type thermocouple
Temperature input range
J type : -100
℃
~700
℃
K type : -100
℃
~1000
℃
R type : -10
℃
~1700
℃
S type : -10
℃
~1700
℃
T type : -100
℃
~350
℃
J type : -148
℉
~1292
℉
K type : -148
℉
~1832
℉
R type : -14
℉
~3092
℉
S type : -14
℉
~3092
℉
T type : -148
℉
~662
℉
Digital conversion range
J type : K-1000~K7000
K type : K-1000~K10000
R type : K-100~K17000
S type : K-100~K17000
T type : K-1000~K3500
J type : K-1480~K12920
K type : K-1480~K18320
R type : K-140~K30920
S type : K-140~K30920
T type : K-1480~K6620
Resolution
14 bits(0.1
°
C)
14 bits(0.18
°
F)
Overall accuracy
±
0.5% of full scale of 25
°
C(77
°
F),
±
1% of full scale during 0~55
°
C
(32~131
°
F)
Response time
350 ms
×
channels
Isolation Method
Isolation between digital and analog circuitry. There is no isolation
between channels.
Digital data format
2’s complement of 16-bit, (13 Significant Bits)
Average function
Yes (CR#2~CR#5 may be set and the range is K1~K4096)
Self diagnostic function
Yes
Communication mode (RS-485)
MODBUS ASCII/RTU Mode. Communication baud rate of 4800 / 9600 /
19200 / 38400 / 57600 / 115200. For ASCII mode, date format is 7Bits,
even, 1 stop bit (7 E 1). For RTU mode, date format is 8Bits, even, 1 stop
bit (8 E 1). The RS-485 is disabled when the DVP04AD-S is connected in
series to an MPU.
Connection to a DVP-PLC MPU in
series
When DVP04-TC modules are connected to an MPU, the modules are
numbered from 0 – 7. 0 is the closest to the MPU and 7 is the furthest.
The Maximum number of modules is 8 modules and they do not occupy
any digital I/O points of the MPU.
3.2 Other Specification
Power Specification
Maximum Power Consumption
2W at 24 VDC (20.4VDC~28.8VDC) ( -15 % ~ +20 %)
Environment Condition
Environment Condition
Follow the DVP-PLC MPU.
4
CR (CONTROLLED REGISTER)
DVP-04TC platinum temperature sensors
Explanation
CR
No.
RS-485
Parameter
address
Latched
Register name
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#0
H 4096
○
R
Model type
System used,. DVP-04TC model code = H 8B
#1
H 4097
○
R/W Thermocouple type
Reserved
CH4
CH3
CH2
CH1
Example: Setting of CH1
1. b2~b0: set (0,0,0) to use J-type
2. b2~b0: set (0,0,1) to use K-type
3. b2~b0: set (0,1,0) to use R-type
4. b2~b0: set (0,1,1) to use S-type
5. b2~b0: set (1,0,0) to use T-type
#2
H 4098
○
R/W CH1 average number
The number of readings used for “average” temperature on channels
CH1~CH4.
Setting range is K1~K4096 and factory setting is K10.
#3
H 4099
○
R/W CH2 average number
#4
H 409A
○
R/W CH3 average number
#5
H 409B
○
R/W CH4 average number
#6
H 409C
╳
R
CH1 average degrees(
°
C)
Average degrees for channels CH1~CH4. (unit: 0.1 degrees C)
#7
H 409D
╳
R
CH2 average degrees(
°
C)
#8
H 409E
╳
R
CH3 average degrees(
°
C)
#9
H 409F
╳
R
CH4 average degrees(
°
C)
#10 H 40A2
╳
R
CH1 average degrees(
°
F)
Average degrees for channels CH1~CH4. (unit: 0.1 degrees F)
#11
H 40A3
╳
R
CH2 average degrees(
°
F)
#12 H 40A4
╳
R
CH3 average degrees(
°
F)
#13 H 40A5
╳
R
CH4 average degrees(
°
F)
#14 H 40A8
╳
R
Present temperature of
CH1 (
°
C)
Present temperature of channels CH1~CH4. (unit: 0.1 degrees C)
#15 H 40A9
╳
R
Present temperature of
CH2 (
°
C)
#16 H 40AA
╳
R
Present temperature of
CH3 (
°
C)
#17 H 40AB
╳
R
Present temperature of
CH4 (
°
C)
#18
Reserved
#19 H 40AE
╳
R
Present temperature of
CH1 (
°
F)
Present temperature of channels CH1~CH4. (unit: 0.1degrees F)
#20 H 40AF
╳
R
Present temperature of
CH2 (
°
F)
#21 H 40B0
╳
R
Present temperature of
CH3 (
°
F)
#22 H 40B1
╳
R
Present temperature of
CH4 (
°
F)
#23
Reserved
#24 H 40AE
○
R
CH1 OFFSET Value
Adjust offset value of channels CH1~CH4. The range is -1000~+1000 and
factory setting is K0. (unit: 0.1 degrees C)
#25 H 40AF
○
R
CH2 OFFSET Value
#26 H 40B0
○
R
CH3 OFFSET Value
#27 H 40B1
○
R
CH4 OFFSET Value
#28~#29
Reserved
#30 H 40B4
╳
R
Error status
Data register stores the error status, refer to fault code chart for details.
#31 H 40B5
○
R/W Communication address
setting
RS-485 communication address.
Setting range is 01~255 and factory setting is K1
#32 H 40B6
○
R/W Communication baud
rate setting
Communication baud rate (4800, 9600, 19200, 38400, 57600 and 115200 bps).
b0: 4800 bps (bit/sec).
b1: 9600 bps (bit/sec). (factory setting)
b2: 19200 bps (bit/sec).
b3: 38400 bps (bit/sec).
b4: 57600 bps (bit/sec).
b5: 115200 bps (bit/sec).
b6~b13: Reserved.
b14: switch between low bit and high bit of CRC code (only for RTU mode)
b15: RTU mode.
#33 H 40B7
○
R/W Reset to factory setting
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Definition of ERR
LED
CH4
CH3
CH2
CH1