TECHNICAL DATASHEET

 

CliQ II DIN Rail Power Supply 

24 V 240 W 2 Phase / DRP-24V240W2BN

 

 

 

 

  

All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.

 

  www.DeltaPSU.com (September 2021, Rev. 06)  

 

2

 

Specifications 

Input Ratings / Characteristics 

 

Nominal Input Voltage 

2 x 200-500 Vac (2-Phase) 

200-277 Vac (Single Phase) 

Input Voltage Range 

2 x 180-550 Vac (2-Phase) 

180-305 Vac (Single Phase) 

Nominal Input Frequency 

50-60 Hz 

Input Frequency  Range 

47-63 Hz 

DC Input Voltage Range* 

254-780 Vdc 

Input Current 

< 2.00 A @ 2 x 230 Vac, < 1.00 A @ 2 x 400 Vac 

Efficiency at 100% Load 

> 90.0% @ 2 x 400 Vac 

Max Power Dissipation 

0% load  < 8.5 W @ 2 x 200 Vac, < 9.5 W @ 2 x 500 Vac 

 

100% load  < 26.5 W @ 2 x 200 Vac, < 21.5 W @ 2 x 500 Vac 

Max Inrush Current (Cold Start) 

< 50 A @ 2 x 200 Vac & 2 x 500 Vac  

Leakage Current 

< 3.5 mA @ 500 Vac 

*Safety approval according to IEC/EN/UL 60950-1 and IEC/EN/UL 62368-1. 

 

 

Output Ratings / Characteristics** 

 

Nominal Output Voltage 

 

24 Vdc 

Factory Set Point Tolerance 

 

24 Vdc ± 2% 

Output Voltage Adjustment Range 

 

24-28 Vdc 

Output Current 

 

10.0 A (continuously operating at 24 V) 

12.0 A (Power Boost for 3 seconds at 24 V, refer to the details 

in the Functions section) 

Output Power 

 

240 W (continuously operating at 24 V) 

288 W (Power Boost for 3 seconds at 24 V, refer to the details 

in the Functions section) 

Line Regulation 

 

< 0.5% (@ 200-550 Vac input, 100% load) 

Load Regulation 

 

< 1.0% (@ 200-550 Vac input, 0-100% load) 

PARD*** (20 MHz) 

 

 

< 150 mVpp @ -10°C and above 

< 200 mVpp @ below -10°C 

Rise Time 

 

< 100 ms @ nominal input (100% load) 

Start-up Time 

 

< 1,000 ms @ nominal input (100% load

)

 

Hold-up Time 

 

> 18 ms @ 2 x 230 Vac, 

> 30 ms @ 2 x 400 Vac (100% load

)

 

Dynamic Response  

(Overshoot & Undershoot O/P Voltage) 

 

± 5% @ 180-550 Vac input, 0-100% load 

(Slew Rate: 0.1 

A/μ

s, 50% duty cycle @ 5Hz) 

Start-up with Capacitive Loads 

 

10,000 µF Max 

Functional 

DC OK Relay Contact  30 V / 1 A Max 

The relay is usually closed when the output is normal 

**For power de-rating from 50°C to 70°C, see power de-rating on page 3. 

***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1 

μF ceramic capacitor & 47

 

μF electrolytic capacitor.

 

 

 

 

Содержание DRP-24V240W2BN

Страница 1: ...L N for 24 V 10 A output The DRP 24V240W2BN has safety approvals for single phase and two phase input according to IEC EN UL 60950 1 IEC EN UL 62368 1 and UL 508 safety standards The product features...

Страница 2: ...ge 24 Vdc Factory Set Point Tolerance 24 Vdc 2 Output Voltage Adjustment Range 24 28 Vdc Output Current 10 0 A continuously operating at 24 V 12 0 A Power Boost for 3 seconds at 24 V refer to the deta...

Страница 3: ...0 5 Vac Operating Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 2 500 Meters 8 200 ft for ITE application 0 to 2 000 Meters 6 560 ft for Industrial application Shock Test Non Operating I...

Страница 4: ...ons IEC EN BS EN 62477 1 IEC 62103 Safety Entry Low Voltage SELV IEC 60950 1 Electrical Safety SIQ Bauart EN 62368 1 UL cUL recognized UL 60950 1 and CSA C22 2 No 60950 1 File No E191395 UL 62368 1 an...

Страница 5: ...z 1 4 GHz 2 GHz 3V M 80 modulation 1 KHz 2 GHz 2 7 GHz 1V M 80 modulation 1 KHz Electrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A1 2 kV Surge IEC 61000 4 5 Level 3 Criteria A1 Common Mo...

Страница 6: ...e specified at 25 C ambient and AC x 2 input unless otherwise indicated www DeltaPSU com September 2021 Rev 06 6 Block Diagram Device Description 1 Input terminal block connector 2 Output terminal blo...

Страница 7: ...Environment the device may run into Over Temperature Protection When activated the output voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the lo...

Страница 8: ...for the input voltage range from 200 Vac to 550 Vac Dismounting Fig 2 1 Mounting Snap on the DIN rail as shown in Fig 2 1 1 Tilt the unit upwards and insert it onto the DIN rail 2 Push downwards until...

Страница 9: ...al Mounting 50 mm 1 97 inch above and below the device as well as a lateral distance of 50 mm 1 97 inch to other units Note that the enclosure of the device can become very hot depending on the surrou...

Страница 10: ...om 10 to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush current...

Страница 11: ...IEC branch circuits without additional protection device An external protection device is only required if the supplying branch has an ampacity greater than above Thus if an external protective devic...

Страница 12: ...t circuits When a short circuit is applied the output current will operate in Hiccup mode as shown in the illustration in the OLP OCP section on this page The power supply will return to normal operat...

Страница 13: ...Vout Please note that output voltage Vout from DRR module will be VO output voltage of power supply Vdrop in DRR module Vdrop will vary from 0 60 V to 0 90 V Typical 0 65 V depending on the load curre...

Страница 14: ...C ambient and AC x 2 input unless otherwise indicated www DeltaPSU com September 2021 Rev 06 14 Fig 5 DC Input Operation Connection Diagram DC Input Operation Step 1 Use a battery or similar DC sourc...

Страница 15: ...the user does not profit from fulfilling this standard therefore it is important to know whether it is mandatory to meet this standard for a specific application Attention Delta provides all informati...

Страница 16: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information Delta Electronics DRP 24V240W2BN...

Отзывы: