The power meter uses the number of loops setting, and unused loop parameters will not be displayed. It can be set
1~5 loop. The default value is 5 loop.
Steps of setup are as follows:
1.
Press the ENTER key on the parameter page, the setting starts after the content flashes.
2.
Use UP or DOWN to select the number of loops.
3.
Press ENTER key to save and return to the next parameter page.
※
Press LEFT key and hold 2 seconds to cancel input and return to the previous menu.
4.1.5 Communication Setting (Comm Group)
4.1.5.1 Address (Addr)
Power meter device address setting. The selectable range is 1~247. Broadcast is 255. The default value is 1.
Steps of setup are as follows:
1.
Press ENTER on the parameter page and start setting after the number flashes.
2.
Press UP or DOWN to select the numeric.
3.
Press LEFT key move to next digit.
4.
Repeat step 2 to 3 until finishing setting, press ENTER key to save and return to the next parameter page.
※
Press LEFT key and hold 2 seconds to cancel input and return to the previous menu.
4.1.5.2 Baud Rate (Baud)
Baud rate setting. The selectable range is 1200
、
2400
、
4800
、
9600
、
19200
、
38400 bps. The default value is 9600
bps.
Steps of setup are as follows:
1.
Press the ENTER key on the parameter page, the setting starts after the content flashes.
2.
Use UP and DOWN to select baud rate.
3.
Press ENTER key to finish setting and back to next parameter page.
※
Press LEFT key and hold 2 seconds to cancel input and return to the previous menu.
Содержание DPM-MA1121
Страница 3: ......
Страница 9: ...Delta Multi Circuit Power Meter DPM MA1121 User Manual 1 4 _1 MEMO...
Страница 14: ...Chapter 2 Specifications 2 5 2_ Setting UI interface tree MA1121...
Страница 15: ...Delta Multi Circuit Power Meter DPM MA1121 User Manual 2 6 _2 2 4 Physical Dimensions unit mm inch Rear view...
Страница 34: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...