background image

TECHNICAL DATASHEET

 

CliQ II DIN Rail Power Supply 

24 V 60 W 1 Phase / DRP024V060W1B

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (September 2021, Rev. 11) 

 

1

 

 

Highlights & Features 

  Universal AC input voltage range 

  High Efficiency > 90.0% 

  Power Boost of 150% for 5 seconds 

  Full corrosion resistant aluminium casing 

  Extreme low temperature cold start at -40°C 

  Conformal coating on PCBAs to protect against common 

dust and chemical pollutants 

  Hazardous Locations approval to ATEX and Class I, Div 2 

(DRP024V060W1BA) 

  Certified according to IEC/EN/UL 62368-1 

 

 

Safety Standards 

 

CB Certified for worldwide use 

 

 

Model Number:

   

DRP024V060W1B

 

Unit Weight:

 

 

0.37 kg (0.82 lb) 

Dimensions (L x W x D):

  121 x 32 x 125

 

mm 

 

 

 

 

 

 

 

 

 

 

 

(4.76 x 1.26 x 4.92 inch)

 

 

 

General Description 

The CliQ II DIN rail power supply series from one of the world’s leading power supply companies, Delta Electronics Group, offers output 

voltage of 24  V. These products are encased in rugged yet lightweight full aluminium body that can withstand shock and vibration 

according to IEC 60068-2 standard. The series of single phase products can operate over a wide temperature range of -25°C to +80°C. 

These products also feature universal AC input voltage range from 85 Vac to 264 Vac and the power will not de-rate throughout the entire 

range. Another great feature is the conformal coating on the PCBA which allows selected models to be certified to ATEX and Class I, Div 

2 for use in hazardous locations.  

 

 

Model Information 

CliQ II DIN Rail Power Supply 

 

Model  Number

 

Input Voltage Range

 

Rated Output  Voltage

 

Rated Output  Current

 

DRP024V060W1B

 

85-264 Vac (120-375 Vdc) 

24 Vdc 

2.50 A 

 

 

Model Numbering 

DR

 

P

 

024V

 

060W

 

1

 

B

 

 

DIN Rail 

Power Supply 

Output Voltage  Output Power  Single Phase  CliQ II Series  A - Metal Case, 

      with Class I, Div 2 and ATEX 
N - Metal Case, 

      without Class I, Div 2 and ATEX 

 

 

 

Downloaded from

Arrow.com.

Содержание CliQ II DRP024V060W1B

Страница 1: ...world s leading power supply companies Delta Electronics Group offers output voltage of 24 V These products are encased in rugged yet lightweight full aluminium body that can withstand shock and vibr...

Страница 2: ...et Point Tolerance 24 Vdc 2 Output Voltage Adjustment Range 24 28 Vdc Output Current 2 50 A continuously operating at 24 V 3 75 A Power Boost for 5 seconds at 24 V refer to the details in the Function...

Страница 3: ...power by 2 5 C Operating Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 2 500 Meters 8 200 ft Shock Test Non Operating IEC 60068 2 27 30 G 300 m S for a duration of 18 ms 1 time per direc...

Страница 4: ...1 IEC 62368 1 UKCA BS EN 62368 1 Industrial Control Equipment UL cUL listed UL 508 and CSA C22 2 No 107 1 01 File No E315355 CSA CSA C22 2 No 107 1 01 File No 181564 Hazardous Location ATEX For DRP02...

Страница 5: ...n 1 kHz Electrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A1 2 kV Surge IEC 61000 4 5 Level 3 Criteria A1 Common Mode2 2 kV Differential Mode3 1 kV Conducted IEC 61000 4 6 Level 3 Criteri...

Страница 6: ...ameters are specified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com September 2021 Rev 11 6 Block Diagram Downloaded from Arrow com Downloaded from Arrow com Downloaded from...

Страница 7: ...cription 1 Input terminal block connector 2 Output terminal block connector 3 DC Voltage adjustment potentiometer 4 DC OK control LED Green 5 Universal mounting rail system Dimensions L x W x D 121 x...

Страница 8: ...ode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition 3 In order for the device to function in the man...

Страница 9: ...the unit slightly to ensure that it is secured Fig 2 2 Dismounting To uninstall pull or slide down the latch with screw driver as shown in Fig 2 2 Then slide the power supply unit PSU in the opposite...

Страница 10: ...unplug connectors when power is turned off DO NOT insert any objects into the unit Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected Do not touch the...

Страница 11: ...dy state set value Inrush Current Inrush current is the peak instantaneous input current measured and occurs when the input voltage is first applied For AC input voltages the maximum peak value of inr...

Страница 12: ...pplying branch has an ampacity greater than above Thus if an external protective device is necessary or utilized please refer a minimum value of 8 A B or 4 A C characteristic breaker Power Boost is th...

Страница 13: ...uit is applied the output current will operate in Hiccup mode as shown in the illustration in the OLP OCP section on this page The power supply will return to normal operation after the short circuit...

Страница 14: ...65V depending on the load current and surrounding air temperature The Signal GND in the DRR module is for the built in LED and DC OK signals The Output GND terminals from the two PSU s do not need to...

Страница 15: ...the following step Step 1 The input voltage applied from Line to Neutral is below the maximum rated input The input voltage shall be below 240Vac 10 Step 2 The external protector is needed on N Neutr...

Страница 16: ...tion Delta shall have no liability of indemnification for any claim or action arising from any error for the provided information in the datasheets Customer shall take its responsibility for evaluatio...

Отзывы: