ASDA-B3 Wiring
3-73
3
3.9.4.2 Deactivation status
When both safety signal sources switch back to high, the alarm will not be cleared automatically.
Of all the STO alarms, only AL500 can be cleared with DI.ARST.
STO_A
STO_B
FDBK
SRDY
H
H
L
L
Max. 10 ms
Max. 10 ms
DI.ARST
ARST
AL500
OFF
ON
Close
Open
Note: refer to Section 3.9.4 for the FDBK signal.