ACC-72EX User Manual
Hardware
18
Jumper Settings
Option Identification Jumpers
Item
Comm. Protocol Option
Part Number
JP1
JP2
JP3
JP4
JP5
JP6
JP7
JP8
JP9
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 16
Bit 17
1 PROFIBUS-DP – Master
310-603958-OPT
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
2 PROFIBUS-DP – Slave
311-603958-OPT
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
3 DeviceNet – Master
320-603958-OPT
OFF
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
4 DeviceNet – Slave
321-603958-OPT
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
5 CANopen – Master
330-603958-OPT
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
6 CANopen – Slave
331-603958-OPT
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
7 CC-Link – Slave
351-603958-OPT
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
8 EtherCAT – Master
360-603958-OPT
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
9 EtherCAT – Slave
361-603958-OPT
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
10 EtherNet/IP – Scanner/Master
370-603958-OPT
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
11 EtherNet/IP – Adaptor/Slave
371-603958-OPT
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
12 Open Modbus/TCP
380-603958-OPT
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
13 PROFINET IO – Controller
390-603958-OPT
OFF
ON
OFF
ON
ON
OFF
ON
OFF
OFF
14 PROFINET IO – Device
391-603958-OPT
ON
ON
OFF
ON
ON
OFF
ON
OFF
OFF
E-Point Jumper Settings
Point
Default
Description
E1
1-2
Selection of Reset Polarity Signal for Hilscher Module:
1-2 Selects Low True Reset
2-3 Selects High True Reset
E2
2-3
Selection of UMAC CPU architecture. This selection affects the data bus and provides
contiguous data addressing for the DPRAM:
1-2 Turbo PMAC
2-3 Power PMAC
E3
1-2
Selection of base address for ACC-72EX:
1-2 Selects Y/X:$6C000 - $6FFFF (
Acc72EX[0]
)
2-3 Selects Y/X:$74000 - $7FFFF (
Acc72EX[1]
)
E5
OFF
Connects DPRAM interrupt to UBUS IRQ-1
E6
OFF
Connects DPRAM interrupt to UBUS IRQ-2
E7
OFF
Connects DPRAM interrupt to UBUS IRQ-3