- 31 -
Humidity analog output (T
d
°C)
P#
DESCRIPTION
VALUE
DEFAULT NOTE
026 Minimum °C dewpoint that can be
associated to minimum scale
analog output (x10)
MIN: -400 (-40.0°C)
MAX: P#027
-400
(3)
027 °C dewpoint at minimum scale
analog output (x10)
MIN: P#026
MAX: P#028 – P#030
-300
(3)
028 °C dewpoint at 10V or 20mA
analog output (x10)
MIN: P#027 + P#030
MAX: P#029
800
(3)
029 Maximum °C dewpoint that can be
associated to 10V or 20mA analog
output (x10)
MIN: P#028
MAX: 850 (85.0°C)
850
(3)
030 Minimum °C dewpoint range for
analog output (x10)
MIN: 50 (5.0°C) 200
(3)
(3) The displayed value is the quantity value multiplied by 10 (decimal point not shown)
Humidity analog output (T
ambient
- T
d
°C)
P#
DESCRIPTION
VALUE
DEFAULT NOTE
031 Minimum °C T
a
-T
d
that can be
associated to minimum scale
analog output (x10)
MIN: 0
MAX: P#032
0
(3)
032 °C T
a
-T
d
at minimum scale analog
output (x10)
MIN: P#031
MAX: P#033 – P#035
0
(3)
033 °C T
a
-T
d
at 10V or 20mA analog
output (x10)
MIN: P#032 + P#035
MAX: P#034
400
(3)
034 Maximum °C T
a
-T
d
that can be
associated to 10V or 20mA analog
output (x10)
MIN: P#033
MAX: 450 (45.0°C)
450
(3)
035 Minimum °C T
a
-T
d
range for analog
output (x10)
MIN: 50 (5.0°C) 100
(3)
(3) The displayed value is the quantity value multiplied by 10 (decimal point not shown).
CO
2
analog output (ppm)
P#
DESCRIPTION
VALUE
DEFAULT NOTE
036 Minimum CO
2
ppm value that can
be associated to minimum scale
analog output
MIN: 0
MAX: P#037
0
037 CO
2
ppm value at minimum scale
analog output
MIN: P#036
MAX: P#038 – P#040
0
038 CO
2
ppm value at 10V or 20mA
analog output
MIN: P#037 + P#040
MAX: P#039
5000
039 Maximum CO
2
ppm value that can
be associated to 10V or 20mA
analog output
MIN: P#038
MAX: 5200
5200
040 Minimum CO
2
ppm value for analog
output
MIN: 1000 1000
Содержание HD45 17A
Страница 10: ... 10 3 1 HD45 connection diagrams ...
Страница 11: ... 11 3 2 HD46 connection diagrams ...
Страница 62: ... 62 Dimensions in mm HD45 series HD46 series ...
Страница 63: ... 63 Fixing holes ...