Configuring Input Devices
the device (press the rocker switch) to allow the gateway to learn the device ID. This should
initiate pairing.
c. Once the pairing is complete, command the Learn Mode BV object to Off.
If a FIL object associated with a Device SV object is changed or edited, a controller
reboot is required to clear data from the previous profile.
Manually Pairing an EnOcean Device
If you already know the address of the EnOcean device you want to link to, you can simply open
the Device Address CSV object and manually enter the hexadecimal address as the object value.
Resetting Pairing
To prevent re-pairing the same device, EnOcean learn packets received when the Device
Address CSV has a non-zero value are ignored. If the EnOcean device you want to link to was
previously paired to another device, manually set the Device Address CSV object to 0, then put it
back in Auto mode. The device is now ready to pair.
©
2022 Delta Controls Inc.
13