Baud rates
125 kbps; 250 kbps; 500 kbps
Electrical specification
Voltage
11 ~ 25 VDC, supplied by internal bus from PLC MPU
Current
28mA (typical), 125mA impulse current (24 VDC)
Environment
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Operation
0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage
-25ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)
Vibration/shock
resistance
Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST
Ea)
Certificates
IEC 61131-2, UL508
1.4 Extension Modules Connectable to RTU-DNET
R
T
U
-D
N
E
T
D
V
P
-0
2
D
A
D
V
P
-0
8
S
T
D
V
P
-1
6
S
P
D
V
P
-0
4
A
D
D
V
P
-0
4
T
C
D
V
P
-0
4
P
T
DVP Slim DI/DO extension units connectable to RTU-DNET
Slim DI/DO
(model name)
I/O mapping data
(DeviceNet
→
RTU-DNET)
I/O mapping data
(RTU-DNET
→
DeviceNet)
DVP-08SM11N N/A
8
bits
DVP-08SN11R/T 8
bits
N/A
DVP-08SP11R/T
8 bits
8 bits
DVP-16SP11R/T
8 bits
8 bits
DVP-08ST N/A
8
bits
Special modules connectable to RTU-DNET
Default I/O mapping data
(DeviceNet
→
RTU-DNET)
I/O mapping data
(RTU-DNET
→
DeviceNet)
Special module
(model name)
Start CR
Length (words)
Start CR
Length (words)
DVP-02DA CR#10 2
N/A N/A
DVP-04DA CR#6 4 N/A N/A
DVP-04AD N/A N/A
CR#12
4
DVP-06AD N/A N/A
CR#12
6
Содержание RTU-DNET