background image

                                                                                                                                       

2007-07-09

5011659701-TPG1

 

EME-PG01

 

Pulse Generator Card for VFD-E Series Instruction Sheet

 

 

   

Please thoroughly read this instruction sheet before installing option cards and putting them into use. 

   

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the 
most updated version at http://www.delta.com.tw/industrialautomation.

X

 

Layout

 

PG Card (EME-PG01) 

Pul se Fe ed ba ck

Pulse Outp ut

Y

 Installation

 

 

Make sure that the AC Motor Drive is powered off before operation. 
DO NOT insert or remove the card when the AC Motor Drive is 
powered on. 

 

Please mount the extension card as shown and fix it with the screw 
packed with the card. 

Screw torque: 
Maximum 2kgf-cm

 

 

Terminals Screw Torque: Maximum 2kgf-cm 

 

Wire Length 

Types of Encoder Output 

Maximum Length 

Wire

 

Gauge 

Voltage 

50m 

Open Collector 

50m 

Line Driver 

300m 

Complementary 

70m 

14 ~ 24 AWG 

(2.1 ~ 0.2 mm

)

NOTE

 

 

EME-PG01 needs additional power source DC 5 ~ 24V, as to 
details please refer to table of terminals descriptions. 

 

Only when the extension card is correctly installed on the AC 
Motor Drive, the extension card will be automatically detected. 
The parameters can be set in Group 13. If extension card is not 
installed, only parameters Group 0 ~ Group 10 can be set. 
Refer to Chapter 5: Parameters in the user manual for further 
details. 

Z

 Notes

 

 

Please use a shielded cable to prevent interference. Do not run 
control wires parallel to any high voltage AC power line (200 V and 
above).  

 

The wire length and signal frequency are in inverse proportion. 

 

Always use this product in a clean indoor location free from dust, 
corrosive gas and liquid. 

 

When the relays are used to switch inductive loads (relays, 
contactors, motors, etc), connect an RC network or Varistor parallel 
to the load to suppress voltage spikes. 

 

For safety, it is recommended to use fuses for the circuitry that is 
switched by the relays. The fuse specification must be within the 
specified contact limits. 

 

The ends of wires must be tinned or crimped. 

 

To avoid interference, route the extension card wires separately and 
as far away (at least 15cm) as possible from other control wires, 
motor wires and power wires, etc. Where these wires must cross 
each other, please make sure they are at a 90

angle. 

 

Always use and operate this product within the limit of its 
specifications.

 

[

 

Specification

 

 

Environmental

 

Operating Temperature

-10

o

C to 50

o

C (non-condensing and not frozen)

Storage Temperature 

-20

o

 C to + 60

o

Ambient Humidity 

Less than 90%RH (non-condensing) 

Installation Altitude 

Below 1000m   

Vibration 

Below 20 Hz: Maximum 9.81 m/s

2

 (1G);   

20 ~ 50Hz: Maximum 5.88 m/s

2

 (0.6G) 

 

Terminals Descriptions 

Terminal Symbols

Descriptions

Vcc 

Input Voltage: DC 5 ~ 24V 

When the encoder output type is voltage output, 
input voltage is DC 12 ~ 24V 

0V 

Power source and input signal common 

A , 

B , 

A

B

 

Input signal from the encoder. Input type is selected 
by SW2. It can be 1-phase or 2-phase input.   
Maximum 300KP/sec 

A/O, B/O 

Output signal from the encoder.   
Open collector: max. output DC24V 50mA   

Grounding 

\

 

Types of Encoder Output

 

Types of Encoder 

Output

SW2

Wiring Diagram 

Voltage 

O/P

0V

VCC

OC

TP

 

Line driver

Q

Q

OC

TP

 

Complementary

O/P

0V

VCC

OC

TP

 

R(L1)

S(L2)

T(L3)

NFB

R

S

T

U(T1)

V(T2)

W(T3)

Motor

3~

VFD-E

OC

TP

A

B

Vcc

0V

A

B

A/O
B/O

RPM Meter

*The power source of RPM meter

 is supplied by  the customers. 

0V

A

B

A

B

PG

EME-PG01

 

DC

5~24V

+

-

GND

Vin

O/P

0V

VCC

OC

TP

 

R(L1)

S(L2)

T(L3)

NFB

R

S

T

U(T1)

V(T2)

W(T3)

Motor

3~

VFD-E

OC

TP

A

B

Vcc

0V

A/O
B/O

RPM Meter

*The power source of RPM meter 

 is supplied by the customers.

0V

A

B

A

B

PG

EME-PG01

 

DC

5~24V

+

-

GND

Vin

 

Open 

collector 

Note: Based on the design, the input signal terminals from 

the encoder should be connected to the terminals 
of

A

 and 

B

  on EME-PG01 card, not the terminals of 

A and B, so as to avoid damage to the encoder.

 