1.  Safety Instructions 

 

The device is not recommended to be placed on low thermal conductive surface. For 

example, plastics. 

 

For safety reasons, please ensure the mounted device is kept at ≥ 4mm safety distance at 

all sides from other components and equipments. In addition, to ensure sufficient 

convection cooling, always maintain a distance of ≥ 20mm from ventilated surfaces while 

the device is in operation (Refer to Fig. 3). 

 

Note that the enclosure of the device can become very hot depending on the ambient 

temperature and load of the power supply. Do not touch the device while it is in operation 

or immediately after power is turned OFF. Risk of burning! 

 

Do not touch the terminals while power is being supplied. Risk of electric shock. 

 

Prevent any foreign metal, particles or conductors from entering the device through the 

openings during installation. It may cause: - Electric shock; Safety Hazard; Fire; Product 

failure. 

 

Warning: When connecting the device, secure Earth connection before connecting L and 

N.  When disconnecting the device, remove L and N connections before removing the 

Earth connection. The power supply must be mounted by metal screws onto a grounded 

metal surface. It is highly recommended that the Earth terminal on the connector be 

connected to the grounded metal surface.

 

 

 

2.  Device Descriptions 

Refer to Fig. 1.:

 

 

1     Input & Output terminal block connector 

2  DC voltage adjustment potentiometer 

3  DC OK control LED (Green)  

4  Remote ON/OFF function connector (Option)

 

 

 

3.  Installation of the Device 

A      Side Mounting: Fig. 2 and Fig. 3 show the mounting hole locations for power supply 

assembly onto a metal mounting surface. The power supply shall be mounted on 

minimum of 4 mounting holes using M4 screw of maximum 4mm length (Refer to Fig. 

5). This is to maintain a safety distance between the screw and internal components. 

B      Base Mounting: Fig. 2 and Fig. 3 show the mounting hole locations for power supply 

assembly onto a metal mounting surface. The power supply shall be mounted on 

minimum of 4 mounting holes using M3  or  2  mounting  holes  using  M4  screw of 

maximum 4mm length (Refer to Fig. 5). This is to maintain a safety distance between 

the screw and internal components. 

C      Fig. 2: Connector  

D      Fig. 2: This surface belongs to customer’s end system or panel where the device is 

mounted. 

 

 

Use flexible cable (stranded or solid) of  AWG  No.  20-12.  The  input/output  connectors’ 

allowable current is 23A max per pin. User should calculate and select the suitable wire 

specification (type/quantity/diameter) according to actual output current. The torque at the 

connector shall not exceed 13Kgf.cm. The insulation stripping length should not exceed 

0.275” or 7mm (Refer to Fig. 4). 

 

Recommended mounting torque of the product and its mounting accessories is 6~8Kgf.cm 

(for M3 screw) or 9~12Kgf.cm (for M4 screw). 

 

4.  Installation of Mounting Accessories 

 

Please refer to the requirements in section 3 for the “Installation of the Device”. 

 

PMF-24V200WC

☐☐

 / PMF-24V240WC

☐☐

 

Fig. 4. Wire Type

 

Lug 

Stripped wire 

Fig. 1: Device Descriptions 

PMF-24V200WCA

, PMF-24V240WCA

☐ 

(Standard Terminal Block)

 

 

PMF-24V200WCG

, PMF-24V240WCG

☐ 

(Front Face Terminal Block)

 

 

Fig. 5. Assembly Reference

 

Base Mounting (Horizontal) 

Base Mounting (Vertical) 

Side Mounting (Horizontal) 

Fig. 2. Mounting Orientation

 

Safety Distance 
D1 = 4.0mm Min. 

D2 = 20.0mm Min. 

Fig. 3. Mounting Hole Locations and the Safety Distance

 