This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation & 
wiring, troubleshooting and peripherals. Other detail information about programming and commands is compatible 
with SA/SC/SX series; please see PLC Application Manual. For more information about the optional peripheral, 
please see individual product manual.

 

 

This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric 
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the 
enclosure, so as to avoid the hazard to users and the damage to the PLC. 

 

Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the PLC. 
Check all the wiring prior to power up. To avoid any electromagnetic noise, make sure the PLC is properly 

grounded 

. DO NOT touch terminals when power on.   

 

Introduction

 

Thank you for choosing DELTA’s PLC DVP series. The DVP-SX series is a 10-point (4DI+2DO+2AI+2AO) 

special main processing unit. Besides the same commands and functions as DVP-SA/SX/SC series, 2-CH 

12-bit analog voltage/current input and 2-CH 12-bit analog voltage/current output are all bipolar. There is 

built-in 2-digit 7-segment display corresponds to internal register directly to display PLC station or 

user-defined code.

 

 Product Profile and Outline

 

Status indicator: POWER, RUN, 
ERROR, BAT.LOW 

RUN/STOP switch 

2-digital 7-segment display 

Digital I/O terminal 

DIN rail clip 

Analog I/O terminals 

I/O point indicators 

COM1 (RS-232) (Rx) indicator 

COM2 (RS-485) (Tx) indicator 

10 

COM1 (RS-232)   
Communication port (Slave) 

 

Units: mm

 

11  Nameplate 
12  Expansion port 

13 

Mounting  hold of the expansion 
unit 

14  DIN rail (35mm) 
15  Expansion unit clip 

16 

COM2 (RS-485)   
Communication port 

17  DC Power input 

18 

2 pin removable terminal   
(standard accessory) 

19 

Power input cable   
(standard accessory) 

20  Battery Cover 
21  Battery socket connection 

Battery replacement:

 Please change the battery within 3 minutes, or the 

internal data of the PLC (including the program area, RTC and latched 
registers) could be lost or destroyed.

 

 

22  Battery mount 

ENGLISH 

 

Electrical Specifications

 

 Electrical Specifications

 

 

     

Model   

    Item

 

DVP10SX11R/T 

DVP08SM11N 

DVP08SN11R/T 

DVP08SP11R/T 

DVP16SP11R/T 

Power supply voltage 

MPU: 24V DC (-15% ~ 20%) (with DC input reverse polarity protection),   
Expansion Unit: supplied by the MPU 

Fuse 

2A / 250V AC 

Power Consumption 

5W 

1W 

1.5W 

1.5W 

2W 

Insulation Resistance 

> 5 M

Ω

  at 500 V DC (Between all inputs / outputs and earth) 

Noise Immunity 

ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS: 26MHz~1GHz, 10V/m 

Grounding 

The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N 
(All DVP units should be grounded directly to the ground pole). 

Environment 

Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2;   
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity); D/A output operation: 0°C ~ 50°C 
(temperature) 

Vibration / Shock 
Resistance 

Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 

Weight (approx.) (g) 

138 / 133 

64 

88 / 68 

90 / 70 

96 / 76 

Approvals 

 

 

 

 

Electrical Specification of Input Point

 

Electrical Specification of Output Point

 

Input Type 

DC (SINK or SOURCE) 

Output Type 

Relay-R 

Transistor-T 

Input Current 

24V DC 5mA 

Current 
Specification 

1.5A/1 point 
(5A/COM) 

0.3A/1 point @ 40°C; When the output of Y0 
and Y1 is high-speed pulse, Y0 and Y1 = 
30mA 

Off 

  On,   

X0,X1: above 18.5V DC 
X2,X3: above 16.5V DC 

Voltage 
Specification 

Below 250V 
AC, 30V DC 

30V DC 

Active Level 

On

Off,   

X0~X3 below 8V DC 

75VA 
(Inductive) 

Maximum 
Loading 

90 W 
(Resistive)

 

9W/1 point 

When the output of Y0 and 
Y1 is high-speed pulse, Y0 
and Y1 = 0.9W (Y0 = 32kHz, 
Y1 = 10kHz) 

Responding 

Time 

About 10ms (An 
adjustment range of 0 ~ 20 
ms could be selected 
through D1020 and D1021) 

Responding 
Time 

About 10 ms 

Off

On 20us 

On

Off 30us 

Y0 and Y1 are specified 
points for high-speed pulse 

 Model Name & I/O Configuration

 

Input 

Output 

Point 

Type 

Point 

Type 

Model 

Power 

DI  AI 

DI 

AI 

DO AO 

DO 

AO 

DVP10SX11R 

Relay 

DVP10SX11T 

24V 

DC 

+20% 
-15% 

DC24V/5 mA 

Sink or Source 

-20 ~ 20mA 

range(-1,000 ~ +1,000) 

-10 ~ +10V 

range(-2,000 ~ +2,000)  2 

Resistor 

-20 ~ 20mA 

(range:-2,000 ~ +2,000) 

-10 ~ +10V 

(range:-2,000 ~ +2,000) 

 Installation & Wiring

 

3.1  PLC Mounting Arrangements and Wiring Notes

 

Installation of the DIN rail:

 

The DVP-PLC can be secured to a cabinet by using the 

DIN rail that is 35mm high with a depth of 7.5mm. When 

mounting the PLC on the DIN rail, be sure to use the 

end bracket to stop any side-to-side motion of the PLC, 

thus to reduce the chance of the wires being pulled 

loose. At the bottom of the PLC is a small retaining clip. 

To secure the PLC to the DIN rail, place it onto the rail 

and gently push up the clip. To remove it, pull down the 

retaining clip and gently pull the PLC away from the DIN 

rail. As shown on the right:   

 

When installing the DVP series 

PLC, make sure that it is 

installed in an enclosure with 

sufficient space (as shown 

below) to its surroundings so as 

to allow heat dissipation.

 

DV P

M P

D

D

D

D

D > 50 mm

 

Wiring:

 

22-16AWG

< 1.5mm

 

1.  Please use 22-16AWG (1.5mm) wiring (either single or multiple core) for 

I/O wiring terminals. The specification for the terminals is as shown on 
the left. PLC terminal screws should be tightened to between 1.95 
kg-cm (1.7 in-lbs). Use 60/75°C copper conductor only. 

2.  I/O signal wires or power supply should not run through the same 

multi-wire cable or conduit. 

3.2  Wiring Notes

 

 Power Input Wiring

 

DVP-SX series input power supply is DC input. Please take a note of listed items when operating DVP-SX. 
Series. 

1.  Please make sure the power is at terminals 24V DC and 0V (power range is 20.4V DC ~ 28.8V DC). When 

voltage is lower than 20.4V DC, PLC will stop operating, all outputs will turn Off and ERROR LED will flash 
continuously. 

2.  If the power-off time is less than 10ms, the PLC still operates unaffectedly. If the power-off time is too long or 

the power voltage drops, the PLC will stop operating and all the outputs will be Off. Once the power is 
restored, the PLC will return to operate automatically. (There are latched auxiliary relays and registers 
inside of the PLC, please be aware when programming.) 

DC Input Type 

S/ S

X0

X1

X2

OV

24VDC

DC /DC

2A

5V

20.4V~28.8V

 

 Safety Wiring

 

Since the PLC is in control of numerous devices, motion of either one device could affect the motion of other 

devices, therefore the breakdown of either one device would consequently be detrimental to the whole auto 
control system, and danger will thus be resulted. Please use the recommended wiring below for the power 
input:

 

 

Power supply for AC loads 

 

Power Circuit Protection Fuse (3A)   

 

Power On pilot indicator 

 

Emergency stop 
The machinery must provide a quick manual method 
disconnecting all system power. 

 

Circuit isolation device (System Power Disconnect) 
Utilize the electromagnetic contactor and the relay to be the 
isolation unit of the power circuit to prevent the possible 
instability of the system when the power is supplied on and off. 

 

DVP PLC MPU (main processing unit) 

 

Grounding 

MC

MC

N

L

1

1

2

3

4

5

6

8

G uard
Limit

7

MC

 

 

 

Power supply: 
AC: 100 ~ 240V AC, 50/60Hz 
DC: 24V DC 

 Input Point Wiring

 

The input signal of the input point is the DC power DC input. There are two modes of DC type wiring: SINK and 
SOURCE, defined as follows:

 

Sink = Current flows into the common terminal S/S

 

Source = Current flows out of common terminal S/S

 

Sinkin g

S/S

X0

 

So urcing

S/S

X0

 

 

Loop Equivalent Circuit of Input Point 

Wiring Loop 

DC Type 

  (DC Signal IN)   

SINK Mode 

+24V

24G

S/S

X0

24VDC

SINK

+5V

 

+24V

OV

Sink  Type

X1

X2

S/S

X0

24VDC

 

Loop Equivalent Circuit of Input Point 

Wiring Loop 

DC Type 

  (DC Signal IN)   

SOURCE Mode 

+24 V

24 G

S/ S

X0

24VDC

SOUR CE

+5V

 

Source Type

X1

X2

S/S

X0

+24V

OV

24VD C

 

 Output Point Wiring

 

Y0

RY

LED

C0

R E LAY O UT P U T

L O AD

P OW E R

DVP-**-**-11-R

 

Y0

LED

C 0

TRANSISTOR OUTPUT

LOAD

DVP- **-**-11-T

<0 .3 A

T
R
G

 

1.  There are two kinds of DVP-SX Series PLC output 

modules: Relay and Transistor. For relevant electrical 
specification, please refer to the function specification. 

2.  Be careful with the connection of the common 

terminals when wiring outputs. For example, when 
wiring DVP12SX11R, output terminal Y0 uses one 
common terminal C0, Y1 uses C1, as shown below: 

C0 Y0 C1 Y1

 

Action indication: When the output point is active, the 
corresponding indicator at the front will be on. 

3.  Isolated circuit: The optical coupler is used to isolate 

signals between PLC internal circuits and input 
modules.

 

 Analog Input/Output Point Wiring

 

CH0

100K

250

-10V~+10V

V+
I+

COM

CH1

250

-20mA~+20mA

V+
I+

COM

*3

*2

AG

AG

Current input

Voltage input

Shielded*1

Shielded*1

100K

CH0

CH1

100K

100K

 

Note 1: 

 

Please isolate analog input and other power 
wiring. 

Note 2: 

 

If input signal is in current, please short out 
between V+ and I+ terminals. 

Note 3: 

 

If the noise interference from loaded input wiring 
terminal is significant, please connect a 
capacitor with 0.1 ~ 0.47

µ

F 25V for noise 

filtering. 

V+
I+

COM

CH0

-10V~+10V

*5

CH0

V+
I+

COM

CH1

-20mA~20mA

CH1

24+
24-

DC24V

DC/DC

+15V

-15V

AG

voltage output

current output

AC drive, recorder,
scale valve...

shielding cable *1

shielding cable *4

AC drive, recorder,
scale valve...

terminal of
power module

class 3  grounding
(100  or less)

converter

 

Note 4: 

 

Please isolate analog output and other power 
wiring. 

Note 5: 

 

If the noise interference from loaded input wiring 
terminal is significant, please connect a 
capacitor with 0.1 ~ 0.47

µ

F 25V for noise 

filtering. 

Note 6: 

 

Please connect 

  power module terminal and 

  analog output module terminal to system 

earth point and make system earth point be 
grounded or connects to machine cover. 

Warning

:   

DO NOT wire to the No function terminal 

 

 

 

注意事項 

 

本使用說明書僅提供電氣規格、功能規格、安裝配線、故障排除及周邊裝置部份說明,其它詳細之程式設計

及指令與

SA/SX/SC

系列相容,詳細說明請見

PLC

技術手冊【程式篇】,選購之周邊裝置詳細說明請見該產

品隨機手冊。

 

 

本機為開放型(

OPEN TYPE

)機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊

/

擊意外之外殼配線箱內。另必須具備保護措施(如

特殊之工具或鑰匙才可打開)防止非維護人員操作或意

外衝擊本體,造成危險及損壞。請勿在上電時觸摸任何端子。

 

 

交流輸入電源不可連接於輸入

/

出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。本體上

之接地端子

 

 

務必正確的接地,可提高產品抗雜訊能力。

 

 

產品簡介 

謝謝您採用台達

DVP

系列可程式控制器。

DVP-SX

機種為

10

點(

4DI+2DO+2AI+2AO

)特殊主機,除與

SA/SX/SC

主機具有相同的指令集及功能規格,並具有

2CH

12-bit

類比電壓

/

電流輸入及

2CH

12-bit

類比電壓

/

電流輸

出,同時均具有雙極性電壓

/

電流輸出能力。主機並內建

2

位數的七段顯示模組,直接對應內部暫存器,可用於

顯示站號或客戶自己定義的訊息代碼。

 

 

產品外觀及各部介紹

 

電源、運行錯誤及電池低電壓

指示燈

 

RUN/STOP

開關

 

2

位數七段顯示模組

 

數位

I/O

端子

 

DIN

軌固定扣

 

類比

I/O

端子

 

輸出

/

輸入指示燈

 

COM1 (RS-232) 

通訊接收

(Rx) 

指示燈

 

COM2 (RS-485) 

通訊傳送

(Tx) 

指示燈

 

10 

COM1 (RS-232) 

通訊口

(Slave) 

 

尺寸單位:

mm 

11 

銘牌

 

12 

擴充機連接口

 

13 

擴充機定位孔

 

14  DIN

軌糟

  (35mm) 

15 

擴充機固定扣

 

16 

COM2 (RS-485) 

通訊口

(Master/Slave) 

17 

電源輸入口

 

18  2 pin 

脫落式端子(標準附件)

 

19 

電源輸入連接線(標準附件)

 

20 

電池蓋

 

21 

電池插座連接

 

電池安裝

電池安裝

電池安裝

電池安裝:

:更換電池時,請在

3

分鐘內完成,否則

PLC

內部資料(包含程式

區,萬年曆及停電保持暫存器)有可能會消失或被破壞。

 

 

22 

電池座

 

繁體中文

繁體中文

繁體中文

繁體中文    

 

產品規格

 

 

電氣規格

 

 

 

 

 

 

 

 

 

DVP10SX11R/T 

DVP08SM11N 

DVP08SN11R/T 

DVP08SP11R/T 

DVP16SP11R/T 

電源電壓

 

主機:

24V DC

-15% ~ 20%

)(具直流輸入電源極性反接保護),擴充機:由主機供應

 

電源保險絲容量

 

2A/250V AC 

消耗電力

 

5W 

1W 

1.5W 

1.5W 

2W 

絕緣阻抗

 

5M

以上(所有輸出

/

入點對地之間

  500V DC

 

雜訊免疫力

 

ESD: 8KV Air Discharge 

EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 

Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 

RS: 26MHz ~ 1GHz, 10V/m 

接地

 

接地配線之線徑不得小於電源端

L,N

之線徑(多台

PLC

同時使用時,請務必單點接地)

 

操作

/

儲存環境

 

操作:

0°C ~ 55°C

(溫度),

50 ~ 95%

(濕度);污染等級

儲存:

-25°C ~ 70°C

(溫度),

5 ~ 95%

(濕度);

D/A

輸出操作:

0°C ~ 50°C

(溫度)

 

耐振動

/

衝擊

   

國際標準規範

  IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC68-2-27 (TEST Ea) 

重量(約

, g

 

138 / 133 

64 

88 / 68 

90 / 70 

96 / 76 

認證

 

 

 

 

 

輸入點電氣規格

 

輸出點電氣規格

 

輸 入

形 式

 

直流(

SINK

SOURCE

 

輸出

 

形式

 

繼電器

-R 

電晶體

-T 

輸 入

電 流

 

24V DC 5mA 

電流

 

規格

 

1.5A/1

點(

5A/COM

 

0.3A/1

  @ 40°C 

高速脈波輸出時

, Y0

Y1

30mA 

Off 

 On,   

X0

X1

18.5V DC

以上

 

X2

X3

16.5V DC

以上

 

電壓

 

規格

 

250V AC,30V DC

以下

 

30V DC 

動 作

位 準

 

On 

 Off,   

X0~X3

8V DC

以下

 

75VA

(電感性)

 

最大

 

負載

 

90W

(電阻性)

 

9W/1

 

高速脈波輸出時

 

Y0

Y1

0.9W 

Y0

50KHz

Y1

10KHz

 

反 應

時 間

 

10ms

(由

D1020

D1021

0 ~ 20ms

的調整)

 

反應

 

時間

 

10 ms 

Off 

 On 20us 

On 

 Off 30us 

Y0

Y1

輸出為

 

高速脈波輸出點

 

 

機種型號與

I/O

配置

 

輸入單元

 

輸出單元

 

點數

 

形式

 

點數

 

形式

 

機種

 

電源

 

DI  AI 

DI 

AI 

DO  AO 

DO 

AO 

DVP10SX11R 

繼電器

 

DVP10SX11T 

24VDC 

+20% 

-15% 

DC24V/5 mA 

Sink

Source 

-20 ~ 20mA 

(

範圍:

-1,000 ~ +1,000) 

-10 ~ +10V 

(

範圍:

-2,000 ~ +2,000) 

電晶體

 

-20 ~ 20mA 

(

範圍:

-2,000 ~ +2,000) 

-10 ~ +10V 

(

範圍:

-2,000 ~ +2,000) 