77
Input the speed setting through DCS digital signal;
Communication:
Input the speed setting through communication;
PID:
Input PID Reference value;
2, Send start command
HMI:
Press
to start the MVD.
Digital:
Start the equipment through DCS digital signal.
Communication:
Input the speed setting through communication;
5-3 Stop
The routine stop modes comprise decelerated stop and free stop.
Free stop: The MVD stops outputting voltage, and the motor rotates freely and
decelerates gradually through the load and friction until it stops.
Caution!
It shall be fully considered according to the operation condition
whether the motor is allowed to stop freely.
During free stop, voltage may still exist in the output cables due
to the back EMF generated by the motor.
Stop (decelerated): the MVD stops according to the preset deceleration time.
For the setting of decelerated stop time, see Chapter IV-Description of functional
parameters.