53
configuration:
Number of Cooling
Fan For Reactance
Cabinet Is
Insufficient
4-4 I/O configuration
Table 4-49 Analog input
ID
Parameter
Min
Max
Unit
Default
Description
P0065 Analog input filter
0
65535
10
Average calculation
point
P0200
Speed given analog
input filter bandwidth
0
65535
Hz
5
P0201
Analog input 1
function selection
0
1
1
0-None
1-Speed setting
P0202
Analog input 2
function selection
0
1
0
0-None
1-Speed setting
P0203
Analog input 1 zero
point adjustment
0
65535
6485
6485(4mA)
P0204
Analog input 1
amplitude
adjustment
0
65535
31999
31999(20mA)
P0205
Analog input 2 zero
point adjustment
0
65535
6485
6485(4mA)
P0206
Analog input 2
amplitude
adjustment
0
65535
31999
31999(20mA)
P0224
Average value of
analog input 1
0
P0225
Average value of
analog input 2
0
P0295
Analog input
channels 1 range
0
65535
1523
P0296
Analog input
channels 2 range
0
65535
1523
P0201 and P0202 are used to define the function selection of the 2 analog input
channels.
P0065 and P0200 are used to set filter parameters of the 2 analog input channels.
P0203~P0206 are used to set zero point and amplitude adjustment of the 2 analog input
channels. P0295 and P0296 are used to set range of the 2 analog input channels.
P0224 and P0225 are used to display filtering results of the 2 analog input channels.
The information is read-only information without default.
Содержание MVF2000 Series
Страница 2: ......
Страница 15: ...11 Standard No Standard Name Used With Adjustable Voltage or Adjustable Frequency Controls or Both...
Страница 36: ...Fig 3 15 date time adjust interface HMI System Click HMI System button to enter into HMI System...
Страница 128: ...Annex B MVF2000 Electrical parameters and dimensions table MVF2000 outline drawings shown below w D H...
Страница 131: ...127 Fig 2 Front view Fig 3 Inside view...