26
Chapter 6
Technical Specifications
Chapter 6 : Technical Specifications
Model
1K
2K
3K
Capacity
1000 VA / 800 W
2000 VA / 1600 W
3000 VA / 2400 W
Input
Voltage Range
110-300Vac*
Frequency Range
40Hz ~ 70Hz
Phase
Single phase with ground
Power Factor
≧
0.99 @ nominal voltage (Input Voltage)
Output
Nominal voltage
200**/208**/220/230/240 Vac
Voltage Regulation
±1% (Batt. Mode)
Frequency Range
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range
(Batt. Mode)
50Hz ± 0.25Hz or 60Hz ± 0.3Hz
Overload
Ambient Temp.<35°C
105% ~ 110%:
The UPS shuts down after 10 minutes in bat-
tery mode or transfers to bypass when the utility is normal.
110% ~ 130%:
The UPS shuts down after 1 minute in battery
mode or transfers to bypass when the utility is normal.
>130%:
The UPS shuts down after 3 seconds in battery
mode or transfers to bypass when the utility is normal.
Current Crest Ratio
3:1
Harmonic Distortion
≦
3 % THD (linear load);
≦
6 % THD (non-linear load)
Waveform
(Batt. Mode)
Pure Sinewave
Efficiency
AC Mode
88%
89%
90%