 Layout

 

I/O Card (EME-A22A) 

 

 

 Installation

 

 

Make sure that the AC Motor Drive is powered off before 

operation. DO NOT insert or remove the card when the AC 
Motor Drive is powered on. 

 

Please mount the extension card as shown and fix it with 

the screw packed with the card. 

Screw  torque: 

Maximum 2kgf-cm

 

 

Terminals Screw Torque: Maximum 5kgf-cm 

 

Wire Gauge: 14 ~ 24 AWG (2.1 ~ 0.2 mm

2

)

 

NOTE

 

 

Only when the extension card is correctly installed on 
the AC Motor Drive, the extension card will be 
automatically detected. The parameters can be set in 
Group 12. If extension card is not installed, only 
parameters Group 0 ~ Group 10 can be set. Refer to 
Chapter 5: Parameters in the user manual for further 
details. 

 Specification 

 

Environmental

 

Operating 
Temperature 

-10

o

C to 50

o

C (non-condensing and not 

frozen) 

Storage 
Temperature 

-20

o

C to + 60

o

Ambient 
Humidity 

Less than 90%RH (non-condensing) 

Installation 
Altitude 

Below 1000m   

Vibration 

Below 20 Hz: Maximum 9.81 m/s

2

 (1G) 

20 ~ 50Hz: Maximum 5.88 m/s

2

 (0.6G) 

NOTE

 

 

Always use this product in a clean indoor location free 
from dust, corrosive gas and liquid. 

 

Inputs/Outputs 

 

EME-D33A

 

Terminal 

Symbols

Descriptions 

Input Voltage: 0 ~ 10VDC =0 ~ Maximum 
Output Frequency (Pr.01.00) 
Input Impedance: 100K

Ω

 

Resolution: 12 bits 

AI1 
AI2 

Input Current: DC 0 ~ 20mA=0 ~ Maximum 
Output Frequency (Pr.01.00) 
Input Impedance: 250

Ω

 

Resolution: 12 bits 
Voltage/Current Switch: Please refer to the 
following diagram   
Output Voltage: DC 0 ~ 10V 
Output Impedance: 1K ~ 2M

Ω

 

Resolution: 12 bits 

AO1 
AO2 

Output Current: DC 0 ~ 20mA 
Output Impedance: 0 ~ 500

Ω

 

Resolution: 12 bits 
Voltage/Current Switch: Please refer to the 
following diagram 

ACM 

Analog control signal common 

 

Voltage/Current Switch

 

AVI3

ACI2

AVI4

ACI3

AVO1

ACO1

AVO2

ACO2

 

 Notes 

 

When the relays are used to switch inductive loads (relays, 

contactors, motors, etc), connect an RC network or Varistor 
parallel to the load to suppress voltage spikes. 

 

For safety, it is recommended to use fuses for the circuitry 

that is switched by the relays. The fuse specification must 
be within the specified contact limits. 

 

Please use shielded wires to avoid interferences and 

connect the shield to ground. 

 

The ends of wires must be tinned or crimped. 

 

To avoid interference, route the extension card wires 

separately and as far away (at least 15cm) as possible from 
other control wires, motor wires and power wires, etc. 
Where these wires must cross each other, please make 
sure they are at a 90

angle. 

 

Always use and operate this product within the limit of its 

specifications.