Warning
Please read this instruction sheet carefully before use and follow this instruction to operate the device in order
to prevent damages on the device or injuries to staff.
Switch off the power before wiring.
This instruction sheet only provides introductory information on electrical specification, functions, wiring,
trouble-shooing the peripherals for DVPPF02-H2. Details of PROFIBUS DP protocol are not included in this
sheet. For more information on PROFIBUS DP protocol, please refer to relevant reference or literatures.
DVPPF02-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the
device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device
may occur.
DVPPF02-H2 is to be used for controlling the operating machine and equipment. In order not to damage it,
only qualified professional staff familiar with the structure and operation of if can install, operate, wire and
maintain it.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur.
Check all the wiring again before switching on the power, and DO NOT touch any terminal when the power is
switched on. Make sure the ground terminal
is correctly grounded in order to prevent electromagnetic
interference.
Introduction
Thank you for choosing Delta DVPPF02-H2 PROFIBUS DP communication module. DVPPF02-H2 can
be applied to the connection with DVP-EH2 series PLC MPU in a PROFIBUS DP network. DVPPF02-H2
does not need to be connected to an external power supply. The power will be supplied from DVP-EH2
once it is connected to DVP-EH2.
Features
1. Supports loop-type data exchange between DP master and many slaves.
2. Supports GSD files in PROFIBUS DP network configuration tools.
3. Supports 4 slots in PROFIBUS DP network configuration tools.
4. Auto-detects baud rates; supports Max. 12Mbps.
5. The length of I/O data can be freely configured through PROFIBUS DP network configuration tools.
Max. input data length = 100 words (the sum of 4 slots); Max. output data length = 100 words (the
sum of 4 slots).
6. Error code diagnosis.
Product Profile & Outline
82 [3.228]
9
0
[3
.5
4
3
]
40 [1.575]
7
[0
.2
7
6
]
PO WER
NET
X
1 6
X
1 6
2
3
5
4
6
7
1
8
Unit: mm
1
Extension port
2
Address setup switch
3
POWER indicator
4
NET indicator
5
PROFIBUS DP connector
6
Extension module interface
7
DIN rail clip
8
DIN rail
ENGLISH
Specifications
PROFIBUS DP Connector
Interface
DB9 connector
Transmission
method
High-speed RS-485
Transmission cable
Shielded twisted pair cable
Electrical isolation
500V DC
Communication
Message type
Loop-type data exchange
Equipment ID
0AFE (hex)
Serial transmission
speed supported
(auto-detection)
9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps; 3Mbps; 6Mbps;
12Mbps (bits per second)
Environment
Standards
IEC 61131-2,UL508
Storage/operation
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree 2
Shock/vibration
immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC
68-2-27 (TEST Ea)
Interference
immunity
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz, 1.4GHz ~ 2GHz, 10V/m
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
Certificates
CE, UL
Components
PROFIBUS DP Connector
To connect to PROFIBUS DP network, use standard DP connector for the wiring.
PIN
PIN name
Definition
1
-
Not defined
2
-
Not defined
3
Rxd/Txd-P
Sending/receiving data P(B)
4
-
Not defined
5
DGND
Data reference potential
6
VP
Power voltage - positive
7
-
Not defined
8
Rxd/Txd-N
Sending/receiving data N(A)
9
-
Not defined
1
6
5
9
Address Setup Rotary Switch
The two rotary address setup switches set up the node addresses on
PROFIBUS DP network in hexadecimal form. Setup range: 0x01 ~ 0x7D (0 or
0x7E ~ 0xFF are forbidden).
Rotary switch
x 16
1
x 16
0
Multiple
× 16
× 1
N
O
D
E
A
D
D
R
E
S
S
x1 6
0
x1 6
1
Example:
If you need to set the node address of DVPPF02-H2 as 26 (1A Hex), simply switch the
corresponding rotary switch of x16
1
to “1" and the corresponding rotary switch of x16
0
to”A”.
Switch setting
Description
0x01 ~ 0x7D
Valid PROFIBUS DP address
0 or 0x7E ~ 0xFF
Invalid PROFIBUS DP address
Note:
The changed values on switches are
only valid when DVPPF02-H2 is re-powered.
When DVPPF02-H2 is operating, changing
the set value of the address will be regarded
invalid.
Extension Port
The extension port on DVPPF02-H2 is used for the connection to the next DVPPF02-H2 or extension
modules of DVP-EH2 series PLC MPU.
Basic Operation
Connecting DVPPF02-H2 to DVP-EH2 Series PLC MPU
S TO P
R UN
0
1
IN
O UT
PO WER
R UN
ER RO R
BAT .L OW
DVP - 2 0E H
x16
0
x16
1
Switch off DVP-EH2. Open the connection
port on the right hand side of DVP-EH2 and
connect DVPPF02-H2 to DVP-EH2. Switch
on DVP-EH2, and DVP-EH2 will supply
power to DVPPF02-H2. There is no need to
connect DVPPF02-H2 to an external power
supply.
Installing DVP-EH2 and DVPPF02-H2 on DIN Rail
x16
0
x16
1
STO P
R UN
0
1
IN
OUT
PO WER
RUN
ERR OR
BAT.LO W
DVP-20EH
1. Use 35mm DIN rail.
2. Open the DIN rail clips on DVP-EH2 and
DVPPF02-H2. Insert DVP-EH2 and
DVPPF02-H2 on the DIN rail.
3. Clip up the DIN rail clips on DVP-EH2
and DVPPF02-H2 to fix DVP-EH2 and
DVPPF02-H2 on the DIN rail.
Connecting to PROFIBUS DP Connector
Insert the PROFIBUS DP bus connector into
the PROFIBUS DP connector on
DVPPF02-H2. Screw it tight to ensure
DVPPF02-H2 and the PROFIBUS DP bus
are properly connected.
Installation & Wiring
1. Install DVPPF02-H2 in an enclosure with sufficient
space around it to allow heat dissipation (see the
figure).
2. DO NOT place the I/O signal wires and power
supply wire in the same wiring circuit.
D>50mm
PF02- H2
D
D
D
D
D
D
E 2 PLC
H
Control Register
The control registers (CR) are the registers inside DVPPF02-H2. See the table below for the definitions of
all the CRs. DVP-EH2 series PLC MPU can read or write the CR allowed through DFROM/DTO
instructions.
CR#
Attribute
Content
High byte
Low byte
#0
Read
Model name
DVPPF02-H2 model code = H
’
0250
#1
Read
Firmware version
Displaying the current firmware version in hex, e.g.
V1.00 is indicated as H’0100.
#2
Read
Length of I/O data
Length of output I/O data Length of input I/O data
#3 ~ #102
Write/read
Input data mapping
Area for storing data from DVPPF02-H2 to
PROFIBUS DP master
#103 ~ #202
Read
Output data
mapping
Area for storing data from PROFIBUS DP master to
DVPPF02-H2.
#203 ~ #206
Set up by the system. DO NOT use it.
#207 ~ #250
Reserved
#251
Read
Error
Register for storing errors. See
for error codes.
#252 ~ #383
Reserved
#384 ~ #511
Set up by the system. DO NOT use it.
LED Indicators & Trouble-Shooting
There are 2 LED indicators on DVPPF02-H2. POWER indicator displays the status of the working power.
NET indicator displays the connection status of the communication.
POWER LED
LED status
Indication
How to deal with it?
Green light on
The power is normal.
--
Off
No power
1. Check if the power of DVP-EH2 is normal.
2. Check if the connection between DVPPF02-H2
and DVP-EH2 is normal.
NET LED
LED status
Indication
How to deal with it?
Off
No power
1. Check if the power of DVP-EH2 is normal
2. Check if the connection between DVPPF02-H2
and DVP-EH2 is normal
Red light on
DVPPF02 is operating but is
not connected to PROFIBUS
DP bus.
Check if DVPPF02-H2 is normally connected to
PROFIBUS DP bus.
Red light
flashes
Depending on the value in
CR#251
See the error code table for how to deal with it.
Green light on
DVPPF02-H2 is in data
exchange status.
--
Error Codes
Code
Description
How to deal with it?
00
DVPPF02-H2 operates normally.
--
01
Hardware error
Send your DVPPF02-H2 back to the factory for
repair.
02
PROFIBUS DP watch dog error
Check if DVPPF02-H2 is normally connected to
PROFIBUS DP bus.
03
Address setup error (0, or exceeding
0x01 ~ 0x7D)
Set the address within the range 0x01 ~ 0x7D and
re-power DVP-EH2.
04
24V low voltage error
Check if the power voltage of DVP-EH2 is normal;
check if DVPPF02-H2 is normally connected to
DVP-EH2.
05
5V low voltage error
Send your DVPPF02-H2 back to the factory for
repair.
注意事項
使用前請務必仔細閱讀本使用手冊,並依照本手冊指示進行操作,以免造成產品受損或人員受傷。
配線時請務必關閉電源。
本使用說明書僅提供電氣規格、功能規格、安裝配線、故障排除及周邊裝置部分說明,本使用說明書僅
作為
DVPPF02-H2
操作指南和入門參考,
PROFIBUS DP
協定的詳細內容這裏不作介紹。如果讀者想瞭
解更多
PROFIBUS DP
協定的內容,請參閱相關專業文章或書籍資料。
本機為開放型機殼,因此使用者使用本機時,必須將其安裝於具防塵、防潮及免於電擊∕衝擊意外的外
殼配線箱內。另必須具備保護措施(如:特殊的工具或鑰匙才可打開),防止非維護人員操作或意外衝
擊本體,造成危險及損壞。
本產品用來控制運轉中的機械及設備。為避免損壞本產品,只有合格且熟悉本產品結構及操作的專業人
員才可進行本產品的安裝、操作、配線及維護。
交流輸入電源不可連接於輸入∕輸出信號端,否則可能造成嚴重損壞。請在上電前再次確認電源配線,
且請勿在上電時觸摸任何端子。本體上的接地端子
務必正確的接地,以提高產品抗雜訊能力。
產品簡介
謝謝您使用台達
DVPPF02-H2
網路通訊模組。
DVPPF02-H2
定義為
PROFIBUS DP
通訊模組,可用於
PROFIBUS DP
網路與
DVP-EH2
系列
PLC
主機的連接,
DVPPF02-H2
無需外接電源,與
DVP-EH2
主機連
接好後由
DVP-EH2
主機提供電源。
功能特色
1.
支持
DP
主站與多個從站之間的迴圈資料傳輸。
2.
在
PROFIBUS DP
網路配置工具中支援
GSD
文檔。
3.
在
PROFIBUS DP
網路配置工具中支援
4
槽
(slot)
配置。
4.
自動偵測通訊速率,最高通訊速率支援
12Mbps
。
5.
I/O
資料長度可通過
PROFIBUS DP
網路配置工具自由配置
,
輸入資料長度總和最大可配置
100
個
word
,
(
4
個
slot
配置長度之和),輸出資料長度總和最大可配置
100
個
word
(
4
個
slot
配置長度之和)。
6.
錯誤碼診斷功能。
產品外觀及各部介紹
82 [3.228]
9
0
[3
.5
4
3
]
40 [1.575]
7
[0
.2
7
6
]
PO WE R
NET
X
1 6
X
1 6
2
3
5
4
6
7
1
8
尺寸單位:
mm
1
擴充模組連接埠
2
位址設定開關
3
POWER LED
指示燈
4
NET LED
指示燈
5
PROFIBUS DP
通訊連接器
6
擴充模組連接頭
7
DIN
軌固定扣
8
DIN
軌槽
繁體中文
功能規格
PROFIBUS DP
連接器
接頭
DB9
接頭
傳輸方式
高速
RS-485
傳輸電纜
遮罩式雙絞線
電氣隔離
500V DC
通訊
資訊類型
迴圈式資料交換
.
設備
ID
0AFE (hex)
支援串列傳輸速度
(自動偵測)
支持
9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps; 3Mbps; 6Mbps;
12Mbps
(位元∕秒)
環境規格
標準
IEC 61131-2,UL508
標準
操作∕儲存環境
儲存:
-25°C ~ 70°C
(溫度),
5 ~ 95%
(濕度)
操作:
0°C ~ 55°C
(溫度),
50 ~ 95%
(濕度),污染等級
2
耐震動∕衝擊
國際標準規範
IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)
雜訊免疫力
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz, 1.4GHz ~ 2GHz, 10V/m
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
認證專案
CE
認證、
UL
認證
各部分元件介紹
PROFIBUS DP
通訊連接器
與
PROFIBUS DP
網路連接時,使用標準
PROFIBUS DP
連接器進行配線。
接腳
名稱
定義
/
說明
1
-
未指定
2
-
未指定
3
Rxd/Txd-P
接收∕發送資料
P (B)
4
-
未指定
5
DGND
資料參考接地
6
VP
電源電壓
-
正壓
7
-
未指定
8
Rxd/Txd-N
接收∕發送資料
N (A)
9
-
未指定
1
6
5
9