This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation & 
wiring. Other detail infromation about programming and intructions is compatible with SV series; please see PLC 
Application Manual. For more information about the optional peripherals, please see individual product instuction 
shee or “DVP-PLC Application Manual: Special module”. 

 

This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric 
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the 
enclosure, in order to prevent hazard to users or damage the PLC. 

 

Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it may damage the PLC. 
Check all the wiring prior to power up. To prevent any electromagnetic noise, make sure the PLC is properly 
grounded 

. Do NOT touch terminals when power on. 

 Introduction

 

 Product Profile & Outline 

1

2

3

5

9

4

9

6

10

5

4

7

8

 

Open COM1 Cover 

 

 

 

  Communication port cover 

  Extension module connection port cover 

  I/O terminal cover 

  Input indicator 

  Function card/memory card cover 

  Output indicator 

  I/O terminals 

  DIN rail clip 

 

  I/O terminal No. 

  DIN rail (35mm) 

 

3

1

2

6

7

1

2

5

4

8

 

Open COM2 cover 

 

 

 

  Mounting screw 

 

  Memory card port 

  Direct mounting hole 

  POWER/RUN/BAT.LOW/ERROR indicator 

  Battery socket 

  Extension module connection port 

  Function card mounting hole 

 

 
 

ENGLISH 

Removable Terminal Block

COM 2 (RS-485)

RUN / STOP SWITCH

VR 0

VR 1

COM 1 (RS-232)

Ba ttery

 

Remove  RS-485 

terminal 

 

 

Part 

Description 

COM2 (RS-485) 

For both master & slave modes 

RUN/STOP switch 

PLC RUN/STOP control 

VR0 

Enable M1178/corresponding value of D1178 

VR1 

Enable M1179/corresponding value of D1179 

COM1 (RS-232) 

For slave mode 

Battery 

Shall be changed within 1 min. 

 

 Dimension 

4.6 X

2

W

W1

8

0

.0

9

0

.0

82.2

 

 

Model 

W (mm) 

W1 (mm) 

DVP16EH00R2/T2 

113 

103 

DVP20EH00R2/T2 

113 

103 

DVP32EH00R2/T2 

143.5 

133.5 

DVP40EH00R2/T2 

158.8 

153.8 

DVP48EH00R2/T2 

174 

164 

DVP64EH00R2/T2 

212 

202 

DVP80EH00R2/T2 

276 

266 

 

 Specifications 

 

 

Model 

Item

 

16EH00

2  20EH00

2  32EH00

2  40EH00

2  48EH00

2  64EH00

2  80EH00

Power supply 
voltage 

100 ~ 240V AC (-15% ~ 10%); 50/60Hz 

±

 5% 

Fuse capacity 

2A/250V AC 

Power consumption 

50VA 

50VA 

60VA 

60VA 

60VA 

80VA 

80VA 

DC24V current 
supply 

500mA 

500mA 

500mA 

500mA 

500mA 

500mA 

500mA 

Power protection 

DC24V; output short-circuited 

Withstand voltage 

1,500V AC (Primary-Secondary); 1,500V AC (Primary-PE); 500V AC (Secondary-PE) 

Insulation 
resistance 

> 5 M

 (all I/O point-to-ground: 500V DC) 

Noise immunity 

ESD: 8KV Air Discharge; EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 
250V; Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m 

Earth 

The diameter of grounding wire shall not be less than that of L, N terminal of the power. (When 
many PLCs are in use at the same time, please make sure every PLC is properly grounded.) 

Operation/storage 

Operation: 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2 
Storage: -40 ºC ~ 70 ºC (temperature); 5 ~ 95% (humidity) 

Vibration/shock 
immunity 

International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27  (TEST 
Ea) 

Weight (g) 

500/480 

520/500 

652/612 

710/675 

748/688 

836/756 

948/848 

 Input Point Specification

 

24VDC single common port input 

Spec. 

Items 

Low speed   

High speed (200KHz) 

Note 

Input wiring type 

Change wiring from S/S to SINK or SOURCE 

Input indicator 

LED display; light on = ON, light off = OFF 

Input voltage 

24VDC 

Off 

 On 

X0 ~ X7, X12, X13, X16, X17, X20 ~ X47: >

 

18.5V DC 

X10, X11, X14, X15: >

 

16.5V DC 

Active 
Level 

On 

 Off 

X0 ~ X47: <

 

8V DC 

Response time/ 
noise immunity 

10ms 

0.5us 

Input point X0 ~ X7, X10 ~ X17 
can conduct 10 ~ 60ms digital 
filter adjustment 

 Output Point Specification

 

Single common port transistor output 

Spec. 

Items 

Low speed   

High speed* 

Single common port relay 

output 

Max. frequency 

10KHz 

200KHz 

Load ON/OFF control 

Output indicator 

LED display; light on = ON, light off = OFF 

Min. load 

2mA/DC power supply 

Working voltage 

5 ~ 30VDC 

250V AC, 30V DC 

Insulation 

Photocoupler isolation 

Magnetic isolation 

Current 
specification 

0.3A/1 point @ 40ºC 

<1KHz, 0.3A/1 point @ 40°C 

1KHz, 30mA/1 point @ 40°C 

2A/1 point (5A/COM) 

75VA (conductive), 90W 

(resistive) 

Off 

 On: 20us 

Max. output delay 

time 

On 

 Off: 30us 

0.2us 

10ms 

Over-current 
protection 

N/A 

Mechanical life 

N/A 

2×10

7

 times (without load) 

Electrical life 

N/A 

1.5×10

5

 times (5A 30V DC); 

5×10

5

 times (3A 120V AC); 

3×10

4

 times (5A 250V AC) 

*High-speed output points (Y0, Y2) are only in DVP20EH2 and DVP32EH2; high-speed output points (Y0, Y1, Y2, Y3, Y4, Y6) are 
only in DVP40EH2. 

 Installation & Wiring 

3.1 PLC Mounting Arrangements and Wiring Notes 

How to install DIN rail: 

DVP-PLC can be secured to a cabinet by using the DIN rail of 35mm in height and 
7.5mm in depth. When mounting PLC to DIN rail, be sure to use the end bracket to stop 
any side-to-side movement of PLC and reduce the chance of wires being loosen. A small 
retaining clip is at the bottom of PLC. To secure PLC to DIN rail, place the clip onto the 
rail and gently push it up. To remove it, pull the retaining clip down and gently remove 
PLC from DIN rail, as shown in the figure. 

How to screw:

 Please use M4 screw according to the dimension of the product.

 

 

DVP MPU

> 50mm

> 50mm

> 50mm

> 50mm

 

Please install PLC in an enclosure with sufficient space around it to allow heat 
dissipation as shown in the figure.

 

Wiring: 

To suit  M3.5 screw  terminals

Below 6.2

Below 6.2

 

1. Use O-type or Y-type terminal. See the figure in the left hand side for its 

specification. PLC terminal screws should be tightened to 5 ~ 8 kg-cm (4.3 ~ 
6.9 in-Ibs) and please use only 60/75ºC copper conductor. 

2. DO NOT wire empty terminal    •  . DO NOT place the input signal cable and 

output power cable in the same wiring circuit. 

3. DO NOT drop tiny metallic conductor into the PLC while screwing and wiring. 

Tear off the sticker on the heat dissipation hole for preventing alien 
substances from dropping in, to ensure normal heat dissipation of the PLC. 

3.2 Wiring Notes 

 Power Input Wiring 

The power input of DVP-EH series is AC. When operating the PLC, please make sure that: 

1.  The input voltage should be current and its range should be 100 ~ 240V AC. The power should be 

connected to L and N terminals. Wiring AC110V or AC220V to +24V terminal or input terminal will result in 
serious damage on the PLC. 

2.  The AC power input for PLC MPU and I/O extension modules should be ON or OFF at the same time. 

3.  Use wires of 1.6mm (or longer) for the grounding of PLC MPU. The power shutdown of less than 10 ms will 

not affect the operation of the PLC. However, power shutdown time that is too long or the drop of power 
voltage will stop the operation of the PLC and all outputs will go OFF. When the power supply turns normal 
again, the PLC will automatically return to its operation. Please be aware of the latched auxiliary relays and 
registers inside the PLC when programming. 

AC Power Input 

L

 

N

 

2.0 A

DC/DC

 

+5V

 

+24V

 

24G

 

S/S

 

X0

 

X1

 

X2

 

100~240VAC

 

 

0.5A is the maximum power supply for +24V power supply output terminal. DO NOT connect other 
external power supplies to this terminal. Every input terminal requires 6 ~ 7mA to be driven; e.g. the 
16-point input will require approximately 100mA. Therefore, +24V cannot give output to extermal load 
that is more than 400mA. 

 Safety Wiring 

Since a PLC controls many devices, actions of any device may affect actions of other devices, and the 
breakdown of any one device may cause the breakdown of the whole auto-control system and danger. 
Therefore, we suggest you wire a protection circuit at the power input terminal, as shown in the figure below. 

 

 

AC power supply load 

 

Power circuit protection fuse (3A

 

 

Power indicator 

 

Emergency stop 

This button can cut off the system power supply when accidental 
emergency takes place.   

 

 

System circuit isolation device 

The device is made of electromagnetic contactor and relay as the 
switch to prevent the instability of system when the power is 
intermittently supplied.   

 

DVP-PLC (main processing unit) 

 

Earth 

M C

MC

N

L

1

1

2

3

4

5

6

7

8

G u ar d
L im it

MC

 

 

Power supply AC: 100 ~ 240V AC 

 Input Point Wiring 

There are two types of DC inputs, SINK and SOURCE. 

Input point loop equivalent circuit 

Wiring loop 

DC Signal IN 

S/S

X0

Sinking

 

SINK

 mode 

(common port for current 

input S/S) 

24VDC

24G

X0

S/S

+24V

SINK

+5V

 

24G

S/S

X0

X1

X2

+24V

Sink  Type

 

 

Input point loop equivalent circuit 

Wiring loop 

DC Signal IN 

S/S

X0

Sourcing

 

SOURCE

 mode 

(common port for current 

output S/S) 

24VDC

24G

X0

S/S

+24V

SOURCE

+5V

 

24G

S/S

X0

X1

X2

+24V

Source Type

 

 Output Point Wiring 

Relay (R) contact circuit wiring 

Y0

RY

LED

C0

LOAD

POWER

DVP-**-**-**-R

RELAY OUTPUT

 

2

3

1

5

C0 Y0 Y1

C1 Y3 Y4 C2 Y6 Y7

4

MC1

MC2

7

10

3

2

8

9

6

 

 

 

Flywheel diode: To extend the life span of contact 

 

Emergency stop: Uses external switch 

 

Fuse: Uses 5 ~ 10A fuse at the common port of output contacts to protect the output circuit.   

 

Varistor: To reduce the interference on AC load 

 

 

Empty terminal: not in use 

 

DC power supply 

 

Neon indicator 

 

AC power supply 

 

Incandescent light (resistive load) 

 

Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC internal 
program, to ensure safety protection in case of any unexpected errors.   

Transistor (T) contact circuit wiring 

Y0

LED

C0

TRANSISTOR OUTPUT

LOAD

DVP-**-**-**-T

<  0.5A

 

M C1

M C 2

2

3

1

C0 Y 0

Y 1 C1 Y 4 Y 5 Y 6

Y 7

5

4

5

3

4

 

 

 

DC power supply 

 

Emergency stop 

 

Circuit protection fuse 

 

Flywheel diode + inductive load 

 

 

Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC internal 
program, to ensure safety protection in case of any unexpected errors. 

 

注意事項 

 

本使用說明書僅提供電氣規格、功能規格、安裝配線部份說明,其它詳細之程式設計及指令與

SV

系列相容,

詳細說明請見

DVP-PLC

應用技術手冊【程式篇】,選購之週邊裝置詳細說明請見該產品隨機手冊或

DVP-PLC

應用技術手冊【特殊模組篇】。

 

 

本機為開放型

  (OPEN TYPE) 

機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊

/

衝擊

意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意外
衝擊本體,造成危險及損壞。

 

 

交流輸入電源不可連接於輸入/出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。請勿
在上電時觸摸任何端子。本體上之接地端子

 

 

務必正確的接地,可提高產品抗雜訊能力。

 

 

產品簡介

 

 

產品外觀及各部介紹

 

1

2

3

5

9

4

9

6

10

5

4

7

8

 

COM1

上蓋打開

 

 

 

 

 

通訊口上蓋

 

 

擴充機連接口上蓋

 

 

輸出/入端子蓋

 

 

輸入點指示燈

 

 

功能卡/記憶卡上蓋

 

 

輸出點指示燈

 

 

輸出/入端子

 

  DIN

軌固定扣

 

 

 

輸入/輸出端子編號

 

 

固定

DIN

軌糟

  (35mm) 

 

3

1

2

6

7

1

2

5

4

8

 

COM2

上蓋開啟

 

 

 

 

機身固定螺絲

 

 

 

記憶卡插槽

 

 

直接固定孔

 

 

電源、運行、錯誤及電池狀態指示

 

 

電池插槽

 

 

擴充機連接口

 

 

功能卡固定孔

 

 

繁體中文

繁體中文

繁體中文

繁體中文    

脫落式端子

COM 2 (RS-485)

RUN / STOP 

開關

VR 0

VR  1

COM 1 (RS-232)

電池

 

RS-485

端子取出

 

 

 

 

 

 

 

COM2 (RS-485) 

Master/Slave

模式兩用

 

RUN/STOP

開關

 

PLC RUN/STOP

控制

 

VR0 

M1178

啟動

/D1178

對應值

 

VR1   

M1179

啟動

/D1179

對應值

 

COM1 (RS-232) 

Slave

模式使用

 

電池

 

更換電池時,必須在

1

分鐘內完成。

 

 

 

外觀及尺寸

 

4.6 X

2

W

W1

8

0

.0

9

0

.0

82.2

 

 

 

 

 

 

W (mm) 

W1 (mm) 

DVP16EH00R2/T2 

113 

103 

DVP20EH00R2/T2 

113 

103 

DVP32EH00R2/T2 

143.5 

133.5 

DVP40EH00R2/T2 

158.8 

153.8 

DVP48EH00R2/T2 

174 

164 

DVP64EH00R2/T2 

212 

202 

DVP80EH00R2/T2 

276 

266 

 

 

電氣規格

 

 

   

機種

 

項目

 

16EH00

20EH00

32EH00

40EH00

48EH00

64EH00

80EH00

電源電壓

 

100 ~ 240V AC (-15% ~ 10%); 50/60Hz 

±

 5% 

電源保險絲容量

 

2A/250V AC 

消耗電力

 

50VA 

50VA 

60VA 

60VA 

60VA 

80VA 

80VA 

DC24V

供應電流

 

500mA 

500mA 

500mA 

500mA 

500mA 

500mA 

500mA 

電源保護

 

DC24V

輸出具短路保護

 

突波電壓耐受量

 

1,500V AC (Primary-Secondary); 1,500V AC (Primary-PE); 500V AC (Secondary-PE) 

絕緣阻抗

 

5 M

Ω以上

  (

所有輸出

/

入點對地之間

  500VDC) 

雜訊免疫力

 

ESD:  8KV Air  Discharge;  EFT: Power Line:  2KV, Digital  I/O:  1KV, Analog  & Communication  I/O: 
250V; Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m 

接地

 

接地配線之線徑不得小於電源端

L, N

之線徑(多台

PLC

同時使用時,請務必單點接地)

 

操作

/

儲存環境

 

操作:

0°C ~55°C

(溫度),

50 ~ 95%

(濕度),污染等級

2

 

儲存:

-40°C ~70°C 

(溫度),

5 ~ 95%

(濕度)

 

耐振動

/

衝擊

 

國際標準規範

  IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 

重量

  (

), (g) 

500/480 

520/500 

652/612 

710/675 

748/688 

836/756 

948/848 

 

輸入點規格

 

24V DC

單端共點輸入

單端共點輸入

單端共點輸入

單端共點輸入

 

規格

 

項目

 

低速

 

高速

200KHz 

備註

備註

備註

備註

 

輸入接線型式

 

由端子

S/S

變換接線為

SINK

SOURCE 

輸入動作指示

 

LED

顯示;燈亮表示為

ON

,不亮表示為

OFF 

輸入信號電壓

 

24V DC 

Off 

 On 

X0 ~ X7, X12, X13, X16, X17, X20 ~ X47: >

 

18.5V DC 

X10, X11, X14, X15: >

 

16.5V DC 

動作位準

 

On 

 Off 

X0~X47: <

 

8V DC 

反應時間

/

雜訊抑制

 

10 ms 

0.5us 

輸入點

X0  ~  X7

X10  ~ 

X17

可作

10  ~ 60  ms

數位

濾波調整

 