Instruction Sheet

 

Thank you very much for purchasing DELTA CTA series. Please read this instruction sheet before using your CTA 
series to ensure proper operation and please keep this instruction sheet handy for quick reference. 

 

¾

 

DANGER! Caution! Electric Shock! 

¾

 

When the power is on, DO NOT touch the AC terminals in case an electric shock may occur. 

¾

 

Make sure the power is disconnected when you check the unit inside.

 

 

¾

 

CTA series is an OPEN-TYPE device. They are intended for installation completely within an overall panel and are for use 
in counting or timing application. If it will cause serious injury to workers or damage on other equipments when used in a 
dangerous environment, please make sure it is installed in an automatic safety protection device. 

1.

 

 

  

Precaution

 

1.  Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width 7.0mm), hole (diameter 

3.2mm). Screw size: M3x6.5 (with 6.8x6.8 square washer). Recommended tightening torque: 0.4 N.m (4kgf.cm). 
Applicable wire: solid/twisted wire of 2mm

2

, 12AWG to 24 AWG. Please be sure to tighten them properly. 

2.  Prevent dust or metallic debris from falling into the device and cause malfunctions. 
3.  DO NOT modify or uninstall the device. 
4.  DO NOT use empty terminals. 
5.  Make sure the wires are correctly connected to proper terminals. 
6.  Keep away from high-voltage and high-frequency environment during installation in case of interference. 
7.  Prevent using the device in premises which contain: 

Dust or corrosive gas   

High humidity   

High radiation   

Vibration and shock 

8.  CTA series is an open-type device. Make sure to install it in an enclosure to prevent dust, humidity in case of an electric 

shock. 

9.  Please make sure the power cables and signal device are installed correctly before switching on the power; otherwise 

serious damage may occur.

 

10.  DO NOT touch the terminals or repair the device when the power is on; otherwise an electric shock may occur. 
11.  Please wait for one minute after the power is switched off to allow the capacitor to discharge and DO NOT touch the 

internal wiring within this period. 

12.  Use dry cloth to clean the device. DO NOT use acid or alkaline liquid to clean the device. 

2.

 

Display, Indicators and Keys

 

Reset 2 indicator
Reset 1 indicator

Key protect 2 indicator

Output 2 indicator

Key protect 1 indicator

Output 1 indicator

Special function indicator

Lock key

Reset key

Mode and number shift key

PV(Present Value) display

SV(Set Value) display

Timer function indicator

Counter function indicator
Tachometer function indicator

Up/Down key

 

 

™

 

LCD Display and indicators

 

RST 1/2 

Light on when reset signal is detected 

BATCH 

“Batch Counting Mode” in Counter and Tachometer function 

K/P 1/2 

Light on when key-protected mode is enabled 

SET 1 2 

SV1, SV2 display 

OUT 1/2 

Light on when output is executing 

TAC 

Light on when Tachometer function is executing 

H M S 

Hour, minute, second, unit of timer, displayed 
in Timer function 

CNT 

Light on when Counter function is executing 

TOTAL 

“Total Counting Mode” in Counter and 
Tachometer function 

TMR 

Light on when Timer function is executing 

™

 

Key Operation

 

 

Increase and decrease SV or change parameter settings. 

  Left move 1 digit of the selected digit. The indicator of the selected digit will flash. 

MODE

  Save the set parameters or switch among functions. 

LOCK 

Prevent settings from being changed. Key-protected mode still works after the power is switched off. Press 

LOCK

 to enter key-protected mode. In non-key-protected status, press 

LOCK

 to enter Lock 1. In Lock 1, press 

LOCK

 again to enter Lock 2. Press

MODE

and

at the same time to disable key-protected mode. 

(Lock 1

disables the functions of all keys. 

(Lock 2) allows users to change SV and functions of 

RESET

 remain. 

LOCK

 only functions in non-key-protected status. 

RESET 

Clear and reset PV. 

™

 

Modes: Operation Mode and Configuration Mode

 

Operation  When the power is on, the timer/counter/tachometer is in the operation mode. Press

to change SV, or 

to make change on a desired digit. The indicator of the selected digit will flash. After the change is made, 

press

MODE

to save the setting. If SV or parameters are not changed, press

MODE

once to switch between SET1 and 

SET2.

 

Configuration  Press

MODE

 

in operation mode

 

for more than 3 seconds to enter configuration mode. Press

MODE

once to switch 

among parameters. To return to operation mode, press

MODE

for more than 3 seconds.

 

3.

 

Ordering Information

 

CTA

2

3

4

5

6

1

 

n

 Product name

  CTA: Delta Counter/Timer/Tachometer A series 

q

 Preset stage

 

0: 2 preset stage 

o

 Panel size 

4: 48mm x 48mm 1/16DIN 

r

 

Communication

  0: none 

p

 Output 2

 

0: NPN; 1: Relay 

s

 

Power supply

 A: 

AC 

100~240V 

4.

 

 

  

Specification 

Power input   AC 100~240V, 50/60Hz 

Input voltage range   85% to 110%, rated voltage 
Power consumption   Less than 10VA 

External power supply   12Vdc ±10%, 100mA 

Display    Double-line, 6-digit negative transmissive LCD display 

Non-voltage input (NPN): ON impedance 1K ohm max. ON residual voltage: 2V max. 

Input signal  

Voltage input (PNP): High level: 4.5 to 30Vdc, Low level: 0 to 2Vdc 
Relay: SPST max.250Vac, 5A (resistance load) 

Output 1  

Transistor: NPN open collector. When 100mA /30Vdc, residual voltage=1.5Vdc max. 
Relay: SPDT max.250Vac, 5A (resistance load) 

Output 2  

Transistor: NPN open collector. When 100mA /30Vdc, residual voltage=1.5Vdc max. 

Dielectric strength   2000Vac 50/60 Hz for 1 minute 

Vibration resistance   Without damage: 10~55Hz, amplitude=0.75mm, 3 axes for 2 hours 

Shock resistance   Without damage: drop 4 times, 300m/s

2

, 3 edges, 6 surfaces and 1 corner 

Ambient temperature   0 

o

C to +50 

o

Storage temperature   -20 

o

C to +65 

o

Altitude    2000m or less 

Ambient humidity   35% to 85% RH (non-condensing) 

Pollution degree   Degree 2 

5.

 

 

  

Parameters in Configuration Mode 

™

 

Timer

 

 

Select a 
function

 

 

 
 

MODE

 

 

Setup Timer 
function, 
(counting up 
or down) 

 

MODE

 

 

Select 
output 
mode of 
Timer 
 

MODE

 

 

Setup the 
displayed 
unit of timer 
 
 

MODE

 

 

Setup the 
pulse width 
of output 1 
 
 

MODE

 

 

Reset min. 
pulse width 
 
 
 

MODE

 

 

Select input 
type (PNP 
or NPN)   
 
 

MODE

 

Back to 

“select a 

function” 

™

 

Counter

 

   

Select a 
function 
 
 

MODE

 

 

Select 
counting 
modes 
 

MODE

 

 

Setup input 
mode of 
Counter 
 

MODE

 

 

Setup output 
mode of 
Counter (not 
dual output) 

MODE

 

 

Setup dual 
output counting 
mode (dual 
output) 

MODE

 

 

Setup counting 
speed 
 

 

MODE

 

 

Setup the 
pulse width of 
output 1 
 

MODE

 

Back to 

“select a 

function”

 

 

Select input 
type (PNP or 
NPN) 
 

MODE

 

 

Reset min. 
pulse width 
 
 

MODE

 

 

Save data or 
not while 
switching off 
power 

MODE

 

 

Setup pre-scale 
value 
 
 

MODE

 

 

Setup the 
decimal point 
 
 

MODE

 

 

Setup the 
pulse width of 
output 2 
 

MODE

 

™

 

Tachometer 

   

Select a function 
 
 

MODE

 

 

Setup output mode 
of Tachometer 
 

MODE

 

 

Setup counting 
speed 
 

MODE

 

 

Setup the decimal 
point 
 

MODE

 

 

Setup pre-scale value 
 
 

MODE

 

Back to “select a 

function”

 

 

Select input type 
(PNP or NPN) 
 

MODE

 

 

Reset min. pulse 
width 
 

MODE

 

!

Setup the average of 

input data 

 

MODE

 

 

Setup the delay time 
while switching on 
power 

MODE

 

™

 

Timer + Counter Mixed

 

 

Select a 
function 

 
 
 

MODE

 

 

Setup Timer 
function, 
(counting 
up or down) 
 

MODE

 

 

Setup 
output 
mode of   
timer 

 

MODE

 

 

Setup the 
displayed 
unit of 
timer 
 

MODE

 

 

Setup 
input 
mode of 
Counter 
 

MODE

 

 

Setup 
output 
mode of 
Counter (not 
dual output) 

MODE

 

 

Setup 
counting 
speed 
 
 

MODE

 

 

Setup the 
pulse width 
of output 1 
 
 

MODE

 

 

Back to 

“select a 

function”

 

 

Select 
input type 
(PNP or 
NPN) 
 

MODE

 

 

Reset 
min. 
pulse 
width 
 

MODE

 

 

Save data 
or not 
while 
switching 
off power 

MODE

 

 

Setup 
pre-scale 
value 

 

 

MODE

 

 

Setup 
the 
decimal 
point 
 

MODE

 

 

Setup the 
pulse 
width of 
output 2 
 

MODE

 

6.

 

 

  

Timer Function 

There are counting up/down modes, several counting units and output modes to choose from in timer function. 
 

 

Select counting up

 

or counting down

 

 

Setup the output time of timer, from 0 to 99.99 secs. 0= Hold output 

 

Setup output modes 

 

 Setup the counting unit of the timer. 

 

 sec 0.01~9999.99 

 A unit = 10ms. 

Max. counting = 9999.99 secs.

 

 

 sec 0.1~99999.9 

 A unit = 0.1sec. 

Max. counting = 99999.9 secs. 

 

 sec 1~999999 

 A unit = 1 sec. 

Max. counting = 999999 secs. 

 

 min,sec 0.01~9959.99 

 A unit = 0.01 sec.  Max. counting = 5999.99 secs. 

 

 min,sec 0.1~99959.9 

 A unit = 0.1 sec. 

Max. counting = 59999.9 secs. 

 

 min 0.1~99999.9 

 A unit = 0.1 min. 

Max. counting = 99999.9 mins. 

 

 min 1~999999 

 A unit = 1 min. 

Max. counting = 999999 mins. 

 

 hr,min,sec 1~995959 

 A unit = 1 sec. 

Max. counting = 359999 secs (100hr) 

 

 hr,min 1~999959 

 A unit = 1 min. 

Max. counting = 35999999 secs (10000hr) 

 

 hr 1~999999 

 A unit = 1 hr. 

Max. counting = 999999 hrs 

 

Power signal

Start signal

Pause signal

Clear signal

Up

Down

0

0

SV

SV

Signal On Delay 1

t

t

Output signal

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

Up

Down

0

0

SV

SV

Signal On Delay 2

t

t

 

 

Power signal

Start  signal

Pause  signal

Clear  signal

Output  signal

SV

0

Up

Down

SV

0

Signal Off Delay

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

SV

0

Up

Down

SV

0

Signal On

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

Up

Down

SV

SV

0

0

Power On Delay

t

t

t

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

Up

Down

SV

SV

0

0

Power On Delay Hold

t

t

t

t

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

Up

Down

SV

SV

Repeat Cycle

0

0

timer output set as 0

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

Up

Down

 

SV

 

SV

 

Repeat Cycle

t

t

t

 

timer output not set as 0

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

Up

Down

SV

SV

0

0

Repeat Cycle Hold

Timer output set as 0

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

Up

Down

SV

SV

0

0

RCYH timer output not set as 0

t

t

t

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

Up

Down

SV1

SV1

SV2

SV2

0

0

Repeat Cycle 2

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

Up

Down

0

SV

SV

0

Signal Cumulate

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

Up

Down

SV1

SV2

SV1

0

0

SV2

Signal Twin ON-Start

 

 

Power signal

Start signal

Pause signal

Clear signal

Output signal

Up

Down

SV1

SV1

SV2

SV2

0

0

Signal Twin OFF-Start

 

 