Chapter 4 Parameters
|
Revision July 2008, EG03, SW V1.06
4-23
4.3 Description of Parameter Settings
Group 0: User Parameters
: This parameter can be set during operation.
00 - 00
Software Version
Factory setting: Read Only
This parameter displays the software version of AC drive.
00 - 01
AC Drive Status Indication 1
Factory setting: Read Only
This parameter displays the AC drive status.
Code
AC Drive Status
Explanation
00
No fault occurred
01 oc
over
current
02 ov
over
voltage
03 oH
over
temperature
04 oL
overload
05 oL1
electronic
thermal
relay
06
EF (external fault)
EF-DCM is closed
07
occ (AC drive IGBT fault )
IGBT short circuit protection
08
CF3 (CPU failure)
Abnormal A/D reading during self-check
09
HPF (hardware protection
failure)
Hardware protection function activated during self-check.
10
ocA (over current during
acceleration)
Output current exceeds protection level during
acceleration
11
ocd (over current during
deceleration)
Output current exceeds protection level during
deceleration
12
Ocn (over current during
steady state)
Output current exceeds protection level during steady
state operation.
13
GFF (ground fault)
Ground fault protection feature activated
14
Lv (under voltage)
Low input voltage
15
CF1
EEPROM input data is abnormal
16
CF2
EEPROM output data is abnormal
17
bb (base block)
BB is set and activated
18
oL2 (over load 2)
Output current exceeds rated motor current
19 Reserved
20
codE
software or password protection
21
EF1 (external emergency
stop)
EF1 (a multifunction-DCM is enabled)
Содержание AC Motor Drive VFD-G
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 17: ...Chapter 1 Introduction 1 8 Revision July 2008 EG03 SW V1 06 For 150 215HP Frame G Step 1 Step 2 Step 3 Step 4...
Страница 18: ...Chapter 1 Introduction Revision July 2008 EG03 SW V1 06 1 9 For 250 300HP Frame H Step 1 Step 2 Step 3 Step 4...
Страница 23: ...Chapter 1 Introduction 1 14 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 45: ...Chapter 2 Installation and Wiring 2 22 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 51: ...Chapter 3 Keypad and Start Up 3 6 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 141: ...Chapter 4 Parameters 4 90 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...