Configurable and Programmable enteliZONE Controllers
Differences Between Configurable and Programmable enteliZONE Controllers
This topic describes the main differences between these 2 types of controllers.
Using the ORCAview or enteliWEB configuration page, variables and setpoints are entered into
the algorithm and written to the appropriate preset objects (100 to 199 range, 1000+ range for
LINKnet device configuration) in the factory controller database.
In the configurable type of controllers, there are no program (PG) objects.
In the programmable controllers, even though it is recommended that you use the configuration
page to set up your programmable controller, local programming can be used to
by writing to the objects in the 800 to 899 range.
There is a limit to the number of specific object types in these controllers. The number limits are
summarized in the table below. You cannot exceed this number by creating any new objects.
Object Type
Configurable
Programmable
LINKnet objects (LNK)
1
4
Event objects (EV)
0
5
Trend Logs (TL)
4
8
Programs (PG)
0
3
Gateway Translation objects (GWT)
(firmware 2.2 and higher)
0
4
For a complete list of enteliZONE supported object types and the number of instances allowed for
each object, go to the enteliZONE
on the Delta Controls Support web site.
LINKnet Devices
Configurable controllers can only connect to 1 LINKnet device at a time. This LINKnet device has to
have a device address of "1" in order for it to work with the controller algorithm. Multiple LINKnet
devices (up to 4) are only supported by the programmable controllers.
LCD and LINKnet objects are located on the enteliZONE controller and are numbered LCDx001
and LNKx001 respectively where x is the network sensor’s device address.
enteliZONE controllers only support eZNS and BACstat LINKnet network sensors. Other LINKnet
devices like Delta Field Modules (DFM) are not supported.
Содержание eZFC-424R4-24
Страница 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Страница 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Страница 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Страница 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...