Installation
XG0226 - 042220
Vented installation
NO RECESS
COMBUSTIBLE FACING
Enclosure top
IMPORTANT
Leaving the
venting ports
open requires
a minimum
chase height
of 6'
VENTED CHASE
See chart for
opening size
Combustible header
Any material protruding into
gray area must be non-
combustible
Combustible Facing material
(Cement board underneath
optional when using a vented
chase)
Venting
ports
open
back wall must be enclosed (no exposed insulation/vapor barrier)
IMPORTANT
Leaving the
venting ports
open requires
a minimum
chase height
of 6'
Venting ports (shown on a DRL3613)
Vented chase opening is mandatory when you open fireplace vent
ports (all ports must be open).
Vented chase height must be no less than 6'
WARNING
WARNING
1:12
DWG. NO.
SHEET 1 OF 4
WEIGHT:
DRL36
Finish
MATERIAL
Revision / Date
Drawn by
DATE
NAME
3/4/2022
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
Y:\Products\Residential Products\R&D Projects\DelRay\DelRay Lin
ear\MNR36\CAD Drawings\zExample-MNR36 Framing Assembly
Monday, March 7, 2022 7:58:08 AM
SCALE
JL
Description
DRL36-Fireplace
A
Revision
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL 1/32"
TWO PLACE DECIMAL .015"
THREE PLACE DECIMAL .005"
ANGULAR .5
ALL BENDS ARE ASSUMED
TO BE 90 UNLESS NOTED
OTHERWISE.
Vented installations require that the chase inner wall must be
enclosed (no exposed insulation/vapour barrier) Follow local codes
WARNING
DRL36
Min. chase
opening
70sq inch
DRL48
Min. chase
opening
100sq inch
DRL60
Min. chase
opening
100sq inch