Connection examples
This Section shows you connection examples of typical sensors and actuators. It
explains the available connection options and how to configure your sensors and
actuators.
Topics
6.1 Connecting sensors
Measuring voltage at analogue input
Sensors with voltage signal can be directly connected.
The largest measurement range is ± 10V bipolar or 10 V uni-
polar.
The smallest range is ± 156mV bipolar and 156 mV unipolar.
Measuring 20 mA current at analogue input
For sensors with current signals you must connect what is known as a load res-
istor to the device input terminals. Suitable resistors are available as accessories.
Measuring temperatures with a thermocouple at analogue
input
207
Delphin Technology AG
Dezember 2015
Profi
Message Manual
Содержание ProfiMessage
Страница 1: ......
Страница 31: ...ProfiMessage 3 5 4 ADIT 31 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 32: ...ProfiMessage 3 5 5 ADVT 3 5 6 AMDT 32 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 33: ...ProfiMessage 3 5 7 DIOT 3 5 8 IOIT 33 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 234: ...ProfiMessage Block diagram for an analogue input signal 234 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 312: ...ProfiMessage 11 Appendix 11 1 ISO 9001 certificate 312 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 313: ...ProfiMessage 11 2 EC declaration on conformity 313 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 314: ...ProfiMessage 314 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Страница 322: ......