Start position in payload data
l
Byte offset
The length of the payload data, i.e. the size of the data field (DU) of a
PROFIBUS message, is limited to a maximum of 244 bytes. This enables mul-
tiple signals to be transmitted within a message. Enter the starting byte for
this signal's payload data
The maximum possible value of the offset is derived from the bit length of the
data type and is displayed to the right of the numeric field. Input is restricted
to the valid values, and the default is 0