Technicalspecifications
Table 16. Operating temperature de-rating specification
Operating temperature de-rating
Specifications
Up to 35°C (95°F)
Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m (3,117
ft)
Particulate and gaseous contamination specifications
The following table defines the limitations that will help avoid any damages to the IT equipment and/or failure from particulates and
gaseous contamination. If the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage or
failure, you may need to rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility of the
customer.
Table 17. Particulate contamination specifications
Particulatecontamination
Specifications
Air Filtration
Datacenterairfiltrationasdefinedby ISO Class 8 per ISO 14644-1 witha 95%
upper confidence limit.
NOTE:
This conditionappliestodatacenterenvironmentsonly. Air
filtrationrequirementsdonotapplyto ITequipmentdesignedtobeused
outside a data center, in environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or MERV13
filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
NOTE:
This condition applies to datacenterand nondata center
environments.
Corrosive dust
• Air must be free of corrosive dust.
• Residual dust present in the air must have adeliquescent point less than 60%
relative humidity.
NOTE:
This condition applies to datacenterand nondata center
environments.
Table 18. Gaseous contamination specifications
Gaseouscontamination
Specifications
CopperCouponCorrosion
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
SilverCouponCorrosion
<200 Å/month as definedby AHSRAETC9.9.
NOTE:
Maximum corrosive contaminant levels measured at
≤
50% relative humidity.