A
A-8
IP4700 Installation and Service Guide
Technical Specifications and Operating Limits
SPS Technical Specifications
This section lists the technical specifications and operating limits for
the Standby Power Supply (SPS).
SPS Interface
Power
Specifications
Power Consumption
Type
Half-duplex RS-232
Baud rate
9600
Parity
None
Voltage
100 V ac to 240 V ac -10%/+10%
single-phase, 47 Hz to 63 Hz; auto-ranging
Current draw
800 watt 8.5 A max. at 100 V ac
input
(when fully loaded)
Input power
800 watts: (850 watts maximum)
Output Power
800 watts: (800 watts maximum)
Chassis power inlet
IEC 320-C14 Appliance Connector (panel mount)
Chassis power outlet
EC 320-C13 Appliance Connector (panel mount)
Charge times
After full power outage, 45-60 minutes maximum
After off-line storage, 2 hours approximately
Transfer time
20 ms maximum