AC power specifications
Table 41 Input power requirements - single-phase, North American, International, Australian
Specification
North American 3-wire
connection
(2 L & 1 G)
International and
Australian 3-wire
connection
(1 L & 1 N & 1 G)
Input nominal voltage
200–240 VAC ± 10% L- L
nom
220–240 VAC ± 10% L- N
nom
Frequency
50–60 Hz
50–60 Hz
Circuit breakers
30 A
32 A
Power zones
Two
Two
Minimum power requirements
at customer site
(VMAX 250F)
l
One 30 A, single phase drop per zone.
l
Two power zones require 2 drops, each drop rated for 30
A.
l
Two systems in an EMC rack require 4 drops, each drop
rated for 30 A.
Minimum power requirements
at customer site (VMAX
450F, VMAX 850F, VMAX
950F)
l
Three 30 A, single-phase drops per zone.
l
Two power zones require 6 drops, each drop rated for 30
A.
l
PDU A and PDU B require three separate single-phase 30
A drops for each.
a. L = line or phase, N = neutral, G = ground
Best Practices for AC Power Connections
130
Site Planning Guide
VMAX 250F, VMAX 450F, VMAX 850F, VMAX 950F with HYPERMAX OS
Содержание EMC VMAX 250F
Страница 6: ...CONTENTS 6 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 10: ...TABLES 10 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 18: ...Pre planning tasks 18 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 22: ...Delivery and transportation 22 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 34: ...Specifications 34 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 42: ...Physical weight and space 42 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...
Страница 110: ...Optional kits 110 Site Planning Guide VMAX 250F VMAX 450F VMAX 850F VMAX 950F with HYPERMAX OS ...