The activity light flashes to indicate that the spin-up sequence has begun.
Installing the front bezel
Steps
1. Align the bezel with the enclosure.
2. Gently push the bezel into place on the cabinet until it latches.
3. If the bezel has a key lock, lock the bezel with the provided key.
CL5262
Figure 120. Installing the bezel
Verify the operation of a replacement part
Steps
1. From PowerStore Manager, select Hardware.
2. Select the appliance where you replaced the faulted part.
3. From the
Hardware
card, select the view of the system where the part was replaced.
The status of the replacement part should read
Healthy
. If the status is still
Faulted
, wait a few minutes and refresh PowerStore
Manager. If the status does not change, ensure that the part is correctly seated, or contact your service provider.
Replace a faulted drive in a 25-drive expansion
enclosure
Take the following actions to remove a faulted drive from a 25-drive expansion enclosure and install a replacement drive.
Identify a faulted drive from PowerStore Manager
Before you replace a drive, ensure that you have identified its location within the system. Using PowerStore Manager, you can identify and
locate a faulted drive.
Steps
1. From PowerStore Manager, select Hardware.
2. Select the enclosure that contains the faulted drive.
3. From the
Hardware
card, select the faulted drive.
84
Expansion enclosure service procedures