When the hot spare feature is enabled, one of the redundant PSUs is switched to the sleep state.
The active PSU supports 100 percent of the load, thus operating at higher efficiency. The PSU in
the sleep state monitors output voltage of the active PSU. If the output voltage of the active PSU
drops, the PSU in the sleep state returns to an active output state.
If having both PSUs active is more efficient than having one PSU in the sleep state, the active
PSU can also activate the sleeping PSU.
The default PSU settings are as follows:
l
If the load on the active PSU is more than 50 percent, then the redundant PSU is switched to
the active state.
l
If the load on the active PSU falls below 20 percent, then the redundant PSU is switched to
the sleep state.
You can configure the hot spare feature by using the iDRAC settings. For more information about
iDRAC settings, see the
Integrated Dell Remote Access Controller User’s Guide
available at Dell.com/
idracmanuals.
Removing a redundant power supply unit
Before you begin
CAUTION
Many repairs may only be done by a certified service technician. You should only
perform troubleshooting and simple repairs as authorized in your product documentation, or as
directed by the online or telephone service and support team. Damage due to servicing that is
not authorized by Dell is not covered by your warranty. Read and follow the safety instructions
that are shipped with your product.
CAUTION
The system requires one power supply unit (PSU) for normal operation. On power-
redundant systems, remove and replace only one PSU at a time in a system that is powered
on.
1. Follow the safety guidelines listed in the Safety instructions section.
2. Disconnect the power cable from the power source.
3. Disconnect the power cable from the PSU and remove the straps that bundle and secure the
system cables.
4. Unlatch and lift the optional cable management arm if it interferes with PSU removal. For
information about the cable management arm, see the systems rack documentation at
Dell.com/poweredgemanuals.
Procedure
1. Press the release latch and pull the PSU out of the chassis.
Installing and removing system components
154
Dell PowerEdge R430 Owner's Manual
Содержание E28S Series
Страница 1: ...Dell PowerEdge R430 Version 1 Owner s Manual E28S Series A03 ...
Страница 8: ...Contents 8 Dell PowerEdge R430 Owner s Manual ...
Страница 36: ...Dell PowerEdge R430 system overview 36 Dell PowerEdge R430 Owner s Manual ...
Страница 40: ...Documentation resources 40 Dell PowerEdge R430 Owner s Manual ...
Страница 194: ...Using system diagnostics 194 Dell PowerEdge R430 Owner s Manual ...
Страница 200: ...Jumpers and connectors 200 Dell PowerEdge R430 Owner s Manual ...
Страница 216: ...Troubleshooting your system 216 Dell PowerEdge R430 Owner s Manual ...
Страница 220: ...Getting help 220 Dell PowerEdge R430 Owner s Manual ...