Site requirements
This table lists the DS60 site requirements. See
on page 100
for hardware specifications information.
Table 3 Site requirements
Requirement
DS60 Expansion Shelf
Vertical space in standard 19", 4-post rack
5U including a 1U Cable Managements Tray.
Do not use a two-post rack. See the slide rail
and installation documentation in the
packaging for installing in a rack.
Air conditioning
Air conditioning that can cope with the
maximum BTU/hr thermal rating.
Temperature controls
Adequate temperature control with a gradient
(change) not to exceed 30° C in an hour.
Front bezel clearance
1.56 inches (4.0 cm) of unobstructed
clearance.
Back panel clearance
5 inches (12.7 cm) of unobstructed clearance.
Airflow
In a closed or multi-unit rack, ensure that the
unit has adequate airflow. If the equipment is
mounted in an enclosed (as opposed to a
four-post open rack), the front and rear doors
should have 65% minimum open area for
airflow. Whether in an open or enclosed rack,
use filler panels to prevent hot air re-
circulation. The rack design and installation
should take into consideration the maximum
ambient operating temperature of the
equipment, which is 35° C.
Power/grounding
The Power distribution within the rack should
provide a safe electrical earth connection.
Voltage should be 200-240 VAC; 50 or 60 Hz.
Plug four power cords - two from each power
supply into separate branch circuit supplies
for redundancy—one set of cords from one
power supply goes to one branch and the
second set of cords from the other power
supply goes to a different branch. Each
receptacle must be capable of safely
supplying 0.94 amps from each power socket
or 1.87 amps from each socket in case of a
redundant circuit.
DS60 Shelf Installation Overview
10
Data Domain DS60 Expansion Shelf
Hardware Guide
Содержание Data Domain DS60
Страница 1: ...Dell EMC Data Domain DS60 Expansion Shelf Hardware Guide 302 002 100 REV 05 ...
Страница 4: ...Hardware specifications 100 CONTENTS 4 Data Domain DS60 Expansion Shelf Hardware Guide ...
Страница 8: ...Revision history 8 Data Domain DS60 Expansion Shelf Hardware Guide ...
Страница 31: ...Figure 9 Recommended cabling for DD4500 3TB drives Installing the Shelves DD4200 DD4500 and DD7200 cabling 31 ...
Страница 43: ...Figure 19 DD6300 Installing the Shelves DD6300 DD6800 and DD9300 cabling 43 ...
Страница 45: ...Figure 21 DD6800 and DD9300 with HA Installing the Shelves DD6300 DD6800 and DD9300 cabling 45 ...
Страница 46: ...Figure 22 DD6800 with DD Cloud Tier Installing the Shelves 46 Data Domain DS60 Expansion Shelf Hardware Guide ...
Страница 47: ...Figure 23 DD6800 with HA and DD Cloud Tier Installing the Shelves DD6300 DD6800 and DD9300 cabling 47 ...
Страница 53: ...Figure 27 Cabling for HA DD9500 and DD9800systems Installing the Shelves DD9500 and DD9800 cabling 53 ...
Страница 80: ...Installing the Shelves 80 Data Domain DS60 Expansion Shelf Hardware Guide ...
Страница 98: ...Post Installation Tasks 98 Data Domain DS60 Expansion Shelf Hardware Guide ...