7.2 Manual mode
Module Operation in Manual Mode
DG OFF
Warm up
DG ON
Engine
cooling
Start button
Warm up delay expired
Stop button
Engine
cooling
Start the engine
Shutdown Alarm
Warning Alarm
Notification
•
Press the
Stop/Config
button.
•
Press the
Start
button to crank the engine
If the
Start
button is pressed in this mode, the
controller sends a Start command and the genset starts
according to the Start sequence. When the genset loading
voltage and frequency are above the Minimum healthy
thresholds, the Warm-up delay timer starts. At the end of
the Warm-up delay, the Load transfer delay starts and the
genset latches. The running hours stop increasing when a
Stop command is received.
Stop the engine
Shutdown Alarm
Warning Alarm
Notification
•
Press the
Stop/Config
button to stop the running
engine.
•
Press the
Stop/Config
button twice to stop the
engine immediately.
When the
Stop/Config
button is pressed, the
controller opens the genset contactor, and the Engine
cooling time starts. At the end of the Engine cooling time,
the controller initiates the Stop sequence by giving the
Stop command.
If the
Stop/Config
button is pressed during Engine
cooling time, the controller skips the Cooling time and
sends the Stop command immediately.
USER MANUAL 4189341243A UK
Page 43 of 78