Level 2
Range
(OV) Return
(OV RETURN)
100 to 348 V phase-neutral
(OV) Trip
(OV TRIP)
102 to 350 V phase-neutral
Table 6.21
Frequency Monitoring (FREQ MONITOR)
Level 2
Range
Under-frequency
(UF ENABLE)
Enable
Disable
(UF) Trip
(UF TRIP)
10.0 to 59.0 Hz
(UF) Return
(UF RETURN)
11.0 to 60.0 Hz
Over-frequency
(OF ENABLE)
Enable
Disable
(OF) Return
(OF RETURN)
25.0 to 74.0 Hz
(OF) Trip
(OF TRIP)
26.0 to 75.0 Hz
6.2.9 Engine
Table 6.22
Crank Disconnect (CRANK DISCONN)
Level 2
Range
Start Attempts
(START ATTEMPTS)
1 to 9
Disconnect on Oil Pressure Sensor
(DISCONN ON LOP SENS)
Enable
Disable
Monitor Pressure Sensor Before Crank
(MON LLOP BEF CRANK)
Enable
Disable
Pressure Sensor Monitoring Threshold
(DISCONN LOP SENS)
0.5 to 10.0 bar
Monitor Pressure Switch Before Crank
(MON LOP BEF CRANK)
Enable
Disable
Disconnect on Oil Pressure Switch
(DISCONN ON LLOP SW)
Enable
Disable
Pressure Switch Transient Time
(LLOP SW TRANS TIME)
0.0 to 3.0 s
Crank Disconnect At Alt Frequency
(ALT FREQUENCY)
10 to 70 Hz
Crank Disconnect At Engine Speed
(ENGINE SPEED)
150 to 4000 RPM
Disconnect On Charging Alt Voltage
(DISC ON CHG ALT VOLT)
Enable
Disable
Charging Alt Disconnect Volt Threshold
(CHG ALT THRESHOLD)
5.0 to 30.0 V