Level 2
Range
Shutdown
(LOP) Lube Oil Pressure Sensor Calibration
Current: 4 to 20 mA
Pressure: 0.0 to 10.0 bar
6.2.5 Outputs
Table 6.11
Outputs # (OUT #)
Level 2
Range
Source
(SOURCE)
See
Digital output source selection
in this document
On Activation
(ON ACTIVATION)
Energise
De-energise
6.2.6 Timers
Table 6.12
Cranking (CRANKING TIMERS)
Level 2
Range
Crank Hold Time
(CRANK HOLD TIME)
1 to 15 s
Crank Rest Time
(CRANK REST TIME)
2 to 60 s
Manual Start Delay
(MANUAL START DELAY)
0 to 300 s
Auto Start Delay
(AUTO START DELAY)
0 to 43200 s
Table 6.13
General (GENERAL TIMER)
Level 2
Range
Safety Monitoring Delay
(SAFETY MONITOR DELAY)
10 to 60 s
Mains Detect Delay
(MAINS DETECT DELAY)
1 to 300 s
Alternator Detect Delay
(ALT DETECT DELAY)
1 to 30 s
Warm-Up Delay
(WARM-UP DELAY)
0 to 60 s
Return To Mains Delay
(RETN-TO-MAINS DELAY)
0 to 600 s
Engine Cooling Time
(ENG COOL TIME)
0 to 300 s
Stop Action Time
(STOP ACTION TIME)
10 to 120 s
Additional Stopping Time
(ADDN STOPPING TIME)
0 to 120 s
Load Transfer Delay
0 to 60 s