![Deif SGC 120 Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/deif/sgc-120/sgc-120_user-manual_2465265011.webp)
Category
Specifications
Voltage resolution
1 V AC RMS for phase-to-neutral
2 V AC RMS for phase-to-phase
Frequency range
5 to 75 Hz
Frequency accuracy
0.25 % of full scale
Frequency resolution
0.1 Hz
NOTE
For single phase applications, it is mandatory to connect the mains phase and neutral cables to the genset controller's
phase L1 and neutral terminals.
3.6 Digital inputs
Category
Specifications
Controller terminals
10, 11, 12, 21, 22
Number of inputs
5
Type
Negative sensing (connect to ground for activation)
Software configurable options
Low Lub Oil Pressure (LLOP) Switch, High Water Temperature, and more
(see
Controller overview, Configurable parameters
in the
User manual
for
more details).
3.7 Analogue resistive sensor inputs
Category
Specifications
Controller terminals
24 (Engine temperature)
25 (Fuel level sensor)
26 (Oil pressure)
Number of inputs
3
Type
Ratio-metric sensing
Range
10 to 5000 Ω (terminal 24 and 25)
10 to 1000 Ω (terminal 26)
Open circuit detection
Above 1.5 kΩ (terminal 24 and 25)
Above 5.5 kΩ (terminal 26)
Measurement accuracy
±2 % of full scale (up to 1000 Ω)
Connection method
Connect the sensor output terminals between the genset controller terminal
and the battery ground terminal
SCP connection
SCP connections for Analogue inputs 1 to 4*:
Battery
Engine body
Sensor
input
Sensor
common
T erminal 41
Terminal 2
Terminal 1
Supply
SGC 1xx series
Analogue
resistive
sensor
USER MANUAL 4189341226A UK
Page 11 of 72