IMD 100 Integration manual 4189360015 Rev. G
Parameter description
Page 228 of 243
13.3.1 Charger parameters
Info
The charger must be in Setup mode (Sub-object 7) to be configured.
All charger parameters have the same CANopen object ID:
2811
(for proprietary CAN see section
). Sub object is used to identify
the different parameters. The following table lists all available parameters:
Sub
object
ID
Parameter name
Ser. / CAN
Type
Function
Range
Unit
Factory
default
Data
type
Access
1
CHARGE_VOLTAGE_SCALED
Status
Charger actual output voltage
0 .. 65535
0.1 V
N/A
U16
RO
2
CHARGE_CURRENT_SCALED
Status
Charger actual output current
0 .. 65535
0.01 A
N/A
U16
RO
3
UC_CAP
Status
Ultra-capacitor capacity
measurement value
0 .. 65535
1 mF
N/A
U16
RO
4
UC_ESR
Status
Ultra-capacitor total resistance
measurement value
0 .. 65535
1 m
Ω
N/A
U16
RO
5
MON_STATE
Status
Actual state of the charger.
Note: When the charger is in
state zero when in setup mode.
0: Disabled (Initialise)
1: Disabled (Off)
2: Disabled (idle)
3: Disabled (ready)
4: Charging (bulk)
5: Charging (absorption)
6: Charging (float)
7: SE test
8: Disabled (error)
N/A
N/A
U16
RO
6
MON_STAT_TIME
Status
Elapsed present state time.
0 .. 65535
s
N/A
U16
RO