IMD 100 Integration manual 4189360015 Rev. G
Operational procedures
Page 165 of 243
9.17
Using digital inputs and outputs
The digital inputs and outputs are not dependent on the state of the IMD. It is possible to read the
state of a digital input or output, as well as set or reset a digital output no matter which operational
state the IMD is in. Digital outputs D5 to D8 as well as digital inputs 1 and 2 can be also be controlled
by mapping (assigning) logical function to them. When this is done, an output will change state or a
function will be activated/deactivated when an input change state. See section
the description of how to use in the IMD Manager user manual.
9.17.1 Digital outputs
This section describes how to use the digital outputs.
9.17.1.1
Prerequisites
None
9.17.1.2
Activation
IMD Manager:
Click on the “DO x” button of the digital output to toggle it:
CAN/CANopen:
Set the applicable bit in Reg. 0x98 (see section
to “1” (on).
9.17.1.3
Operation
IMD Manager:
The state of all digital outputs is represented by LED in
the “Monitor and control” tab.
The LED is turned ON when the output is ON, and Off when the output is Off.
CAN/CANopen:
The state of all digital inputs can be retrieved from object 2098 (see section