DPS-1 Installation and operation instructions 4189360002 Rev. C
Electrical connections
Page 11 of 14
5.2
General recommendations
It is recommended to use ferrules on the wires before connecting it to the connector. The
length of ferrule (termination sleeve) is the uninsulated part of the ferrule:
Ferrule length
Figure 4
Ferrule length definition
Follow the ferrule manufacturer instruction on how to use a ferrule.
5.3
Connecting wires to connectors
Table 2
Technical data for all connectors (D-ZFKDS 2.5)
Conductor cross section flexible, without ferrule
0.2 to 2.5 mm
2
Conductor cross section flexible, with ferrule without plastic sleeve
0.2 to 2.5 mm
2
Conductor cross section flexible, with ferrule with plastic sleeve
0.2 to 2.5 mm
2
Stripping length
8 mm
Ferrule length
8 mm
To connect wires to terminals:
1. Use a flat screwdriver and press the spring in as illustrated (pos.1 and 2)
2. Press the wire all the way in (pos.3).
3. Lift the screwdriver (pos.4).
Attention
Ferrules are mandatory if multiple wires are connected to the same terminal. Use
the same length as for single wire.
2
1
3
4